9
DEDICATED INSTRUCTIONS
9.9 JP/GP.SEND
9
- 91
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
(b) Devices used in the program example
1) Link special relay (SB) and link special register (SW)
* 1 Used when the target station is on a redundant system.
Remark
For details about link special relay (SB) and link special register (SW), refer to the
following.
• Appendix 1 Link Special Relay (SB) List
• Appendix 2 Link Special Register (SW) List
2) Devices used by the user
(c) SEND instruction settings
Control data settings for the SEND instruction are shown below.
Table 9.49 Link special relay (SB) and link special register (SW)
Device
Description
Device
Description
SB0047
Baton pass status (own station)
SW01F0.1
Redundant system status (3) of station No.2
*1
SW00A0.1
Baton pass status of station No.2
SW01F0.2
Redundant system status (3) of station No.3
*1
SW00A0.2
Baton pass status of station No.3
*1
—
Table 9.50 Devices used by the user
Device
Description
Device
Description
M150
Control data setting command
M156
Completion status indication device
M151
Send data setting command
D350 to
D367
Control data
M152
Start contact
D612
Error code storage device
M155
Completion device
D750 to
D753
Send data storage device (station No.1)
Table 9.51 SEND instruction settings
Device
Item
Set value
(S1)+0
D350
Execution/Error completion
type
0081
H
(With arrival confirmation, clock
data at the time of error completion is
set.)
(S1)+1
D351
Completion status
—
(Set by the system, no setting required)
(S1)+2
D352
Channel used by own station
3
(S1)+3
D353
Target station channel
5
(S1)+4
D354
Target station network No.
1
(S1)+5
D355
Target station No.
2 (2 or 3 when the target station is on a
redundant system)
(S1)+6
D356
(Unused)
0
(S1)+7
D357
Number of resends
5 times
(S1)+8
D358
Arrival monitoring time
0 (10 seconds)
(S1)+9
D359
Send data length
4 words
(S1)+10
D360
(Unused)
0
(S1)+11
D361
Clock set flag
—
(Set by the system, no setting required)
(S1)+12 to
(S1)+15
D362 to D365
Clock data on error completion
(S1)+16
D366
Error-detected network No.
(S1)+17
D367
Error-detected station No.