App
- 32
Appendix 2 Link Special Register (SW) List
APPENDICES
SW0140 to
SW0147
IN-side error frame
reception detection
status
Stores whether the error frame is received or not in the IN-side transmission
path of each station from power-on to the present.
The stored value is cleared when Clear IN-side transmission error count
(SB0007) is turned ON.
0: Error frame not received
1: Error frame received
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
• Valid only for the normally operating station at Baton pass status of each
station (SW00A0 to SW00A7).
SW0150 to
SW0157
OUT-side error frame
reception detection
status
Stores whether the error frame is received or not in the OUT-side
transmission path of each station from power-on to the present.
The stored value is cleared when Clear OUT-side transmission error count
(SB0008) is turned ON.
0: Error frame not received
1: Error frame received
(Condition)
• Valid when Baton pass status (own station) (SB0047) is OFF.
When Baton pass status (own station) (SB0047) is turned ON (error), data
prior to error is held.
• Valid only for the normally operating station at Baton pass status of each
station (SW00A0 to SW00A7).
Table App.4 Link special register (SW) list (Continued)
No.
Name
Description
Availability
Control
station
Normal
station
SW0141
SW0142
SW0143
SW0144
SW0145
SW0146
SW0147
SW0140 16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
-
-
-
-
-
-
-
-
120 119 118 117 116 115 114 113
Each number in the table represents station No.
SW0151
SW0152
SW0153
SW0154
SW0155
SW0156
SW0157
SW0150 16 15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
80 79 78 77 76 75 74 73 72 71 70 69 68 67 66 65
96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81
112 111 110 109 108 107 106 105 104 103 102 101 100 99 98 97
-
-
-
-
-
-
-
-
120 119 118 117 116 115 114 113
Each number in the table represents station No.
Link special register (SW): SW0140 to SW0157