10.2 Error Code List
10
- 21
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
10
TROUBLESHOOTING
E26C
H
Channel busy (Dedicated
instruction)
The channel specified for "Channel
used by the own station" or "Target
station channel" is being used for
another instruction.
• Wait for a little while, and retry it.
• Change the setting of "Channel used by the own
station" or "Target station channel" in the control
data.
E26D
H
Interrupt setting channel
duplication (Dedicated
instruction)
The channel specified for "Channel
used by the own station" is
duplicated with the channel used for
the interrupt setting.
• Check and correct the Channel used by the own
station in the control data, and retry the
instruction.
• Check and correct the channel used for the
interrupt setting, and retry the instruction.
• If the error persists even after taking the above
action, please consult your local Mitsubishi
representative.
E26E
H
Device specification error
(ZNRD/ZNWR instruction)
The device range specified in the
setting data for the ZNRD/ZNWR
instruction is not correct.
• Check the setting data of the ZNRD/ZNWR
instruction, and then retry the instruction.
• If the error persists even after taking the above
action, please consult your local Mitsubishi
representative.
E26F
H
E270
H
Network module error
The hardware has failed.
• Please consult your local Mitsubishi
representative.
E271
H
Operation mode error (RSTOP
instruction)
The Operation mode for the RSTOP
instruction is not set correctly.
• Check and correct the Operation mode setting in
the setting data, and then retry the instruction.
• If the error persists even after taking the above
action, please consult your local Mitsubishi
representative.
E272
H
Clear mode error (RRUN
instruction)
The Clear mode for the RRUN
instruction is not set correctly.
• Check and correct the Clear mode setting in the
setting data, and then retry the instruction.
• If the error persists even after taking the above
action, please consult your local Mitsubishi
representative.
E273
H
Mode error (RRUN instruction)
The Mode for the RRUN instruction
is not set correctly.
• Check the Mode setting in the setting data, and
then retry the instruction.
• If the error persists even after taking the above
action, please consult your local Mitsubishi
representative.
E274
H
to
E277
H
Network module error
The hardware has failed.
• Please consult your local Mitsubishi
representative.
E280
H
to
E288
H
E2A0
H
Receive buffer full (Transient)
Too many transient requests have
been received from CC-Link IE
controller network compatible
devices.
• Adjust the timing of transient requests from
CC-Link IE controller network compatible
devices so that each request will issued at
certain intervals.
E2A1
H
Send buffer full (Transient)
E2A2
H
Transmission completion wait
time timed out
Timeout has occurred without
transmission completion.
• Check the network status in the CC IE Control
Network Diagnostics.
• If the error persists even after taking the above
action, please consult your local Mitsubishi
representative.
Table 10.1 Error Code List (Continued)
Error code
Error
Error detail
Corrective action