(9) Checking parameter status
The reflection status and setting contents of parameters can be checked with link
special relay (SB) and link special register (SW).
(a) Checking parameter status of other stations
1) Check the following link special relay (SB) and link special register (SW) with
the master station.
• When receiving parameters is completed, Parameter communication
status of each station (SB00D0) is turned OFF.
• Stations that are still communicating parameters can be checked with
Parameter communication status of each station (SW00D0 to SW00D7).
2) Check the following link special relay (SB) and link special register (SW) with
the master station.
• When parameters have an error, Parameter status of each station
(SB00E0) is turned ON.
• The station No. of the faulty station is stored in Parameter error status of
each station (SW00E0 to SW00E7).
3) Details of the parameters for each station can be checked with the link special
relay (SB) and link special register (SW) of each station.
Table 8.29 SB/SW used in checking parameter status of other stations
No.
Description
No.
Description
SB00D0
Parameter communication status of each station
SW00D0 to
SW00D7
Parameter communication status of each station
SB00E0
Parameter status of each station
SW00E0 to
SW00E7
Parameter error status of each station