9
DEDICATED INSTRUCTIONS
9.20 J(P)/G(P).RIWT
9
- 179
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
(6) Program example
In this program example, when M210 turns ON, data in D850 to D853 of station No.2
(own station) are written to D1100 to D1103 of station No.3 (target station).
(a) System configuration example
(b) Devices used in the program example
1) Link special relay (SB) and link special register (SW)
Remark
For details of link special relay (SB) and link special register (SW), refer to the
following.
• Appendix 1 Link Special Relay (SB) List
• Appendix 2 Link Special Register (SW) List
2) Devices used by the user
Figure 9.156 System configuration example
Table 9.112 Link special relay (SB) and link special register (SW)
Device
Description
Device
Description
SB0047
Baton pass status (own station)
SW00A0.2
Baton pass status of station No.3
Table 9.113 Devices used by the user
Device
Description
Device
Description
M210
Start contact
D420 to
D424
Control data
M211
RIWT executing flag
D626
Error code storage device
M215
Completion device
D850 to
D853
Write data storage device (station No.2)
M216
Completion status indication device
—
D850
D851
D852
D853
D1100
D1101
D1102
D1103
Network No.1
Station No.1
CPU module
CC-Link IE
controller
network
module
Station No.2
Station No.4
Station No.3
CPU module
CC-Link IE
controller
network
module
CPU module
CC-Link IE
controller
network
module
CPU module
CC-Link IE
controller
network
module
Send buffer
RIWT instruction
request source
(Own station)
RIWT instruction
request target
(Target station)
Summary of Contents for QJ71GP21-SX
Page 1: ......
Page 2: ......
Page 644: ...App 94 Appendix 6 External Dimensions Appendix 6 2 QJ71GP21S SX APPENDICES Memo ...
Page 649: ......
Page 650: ......