9
DEDICATED INSTRUCTIONS
9.8 J(P)/G(P).REQ (Reading/Writing Clock Data)
9
- 71
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
(3) Function
(a) REQ instruction overview
The REQ instruction sends request data (S2) to the target station to request for
service.
The target station is specified in Target station network No. ((S1)+4) and Target
station No. ((S1)+5) of control data.
Upon completion of the request to the target station, the completion device (D2)
turns ON.
(b) Target stations available for specification
1) Target network
In addition to CC-Link IE controller network, stations in the following networks
can be also specified.
• MELSECNET/H
• MELSECNET/10
• Ethernet
2) Target station's CPU type
The REQ instruction is executable only when the target station has QCPU or
QnACPU.
The REQ instruction is not executable to the ACPU connected to
MELSECNET/10 or Ethernet.
Figure 9.58 REQ instruction
Clock data
read/write
CC-Link IE controller
network module
CPU module
CPU module
REQ
Network
module
(S2)
Channel 1
Channel n
Channel 8
[Own station]
[Target station]
Summary of Contents for QJ71GP21-SX
Page 1: ......
Page 2: ......
Page 644: ...App 94 Appendix 6 External Dimensions Appendix 6 2 QJ71GP21S SX APPENDICES Memo ...
Page 649: ......
Page 650: ......