3
- 2
3.1 Performance Specifications
3
SPECIFICATIONS
* 1 A Universal model QCPU can be set to a station No. within the range of No.1 to No.120.
For a module other than Universal model QCPUs, station No.1 to No.64 can be set.
* 2 A station with a Basic model QCPU or safety CPU operates as a normal station. (It cannot be set to
a control station.)
* 3 All I/O signals of the CC-Link IE controller network module are used by the system. (Use
prohibited)
* 4 Two I/O slots are occupied.
In the Start I/O No. field of Network parameter, set a value obtained by adding 10
H
to the I/O No. of
the module-installed slot. Note that 0 point can be set instead of 16 points for the first half in I/O
assignment of PLC parameter.
(Example) When the module is installed to slot 0, set 10
H
to Start I/O No. (When 0 point is set to
slot 0 in I/O assignment, set 0
H
to Start I/O No.)
External
power supply
Voltage
No external power supply function
20.4V to 31.2V DC
Current
0.28A
Terminal screw size
M3
Applicable solderless
terminal
R1.25-3
Applicable wire size
0.3 to 1.25mm
2
Tightening torque
0.42 to 0.58N•m
Allowable momentary
power failure time
1ms (Level PS1)
Noise immunity
By noise simulator of 500Vp-p noise voltage,
1 s noise width, and 25 to 60Hz noise frequency
Internal current consumption (5V DC) 0.85A
0.90A
External dimensions
98 (H) x 27.4 (W) x 90 (D) [mm]
98 (H) x 55.2 (W) x 90 (D) [mm]
Weight
0.18kg
0.28kg
Table 3.1 Performance specifications (Continued)
Item
Specification
QJ71GP21-SX
QJ71GP21S-SX
Summary of Contents for QJ71GP21-SX
Page 1: ......
Page 2: ......
Page 644: ...App 94 Appendix 6 External Dimensions Appendix 6 2 QJ71GP21S SX APPENDICES Memo ...
Page 649: ......
Page 650: ......