App
- 68
Appendix 4 Comparison between CC-Link IE controller network and MELSECNET/H
Appendix 4.4 Precautions for system replacement
APPENDICES
Replace the station-specific parameters in the previous page with refresh parameters.
(5) END processing time of CPU module
If a sequence program used for MELSECNET/H is utilized in CC-Link IE controller
network, the END processing time of the CPU module is increased due to the
influence of the link refresh time. (The network parameter settings (number of
stations, network range assignment, etc.) are assumed to be the same.)
Reducing the link refresh points can shorten the END processing time of the CPU
module.
Figure App.3 Setting example of refresh parameters
Figure App.4 Assignment with link refresh
Table App.28 END processing time of CPU module
Condition for use in MELSECNET/H
END processing time of CPU module
Instruction execution time in sequence scan time > Link scan time
Same as the case where a MELSECNET/H module is mounted.
Instruction execution time in sequence scan time < Link scan time
The END processing time of the CPU module is increased,
compared with the case where a MELSECNET/H module is
mounted.
Since the link scan time in CC-Link IE controller network is short, the
points of cyclic data that are sent from respective stations are
increased.
Because of this, the link refresh time is prolonged and the END
processing time of the CPU module is increased.
Station No.1(a)
Station No.2
Station No.3
Station No.4
Station No.5
Station No.1(b)
Link relay (B)
Link refresh
Link refresh
CPU module
0
FF
100
1FF
200
2FF
300
3FF
400
4FF
500
5FF
CC-Link IE controller network module
Station No.1(a)
Station No.1(b)
Station No.2
Station No.3
Station No.4
Station No.5
Network range assignment (LB)
0
1FF
200
2FF
300
3FF
400
4FF
500
5FF
Summary of Contents for QJ71GP21-SX
Page 1: ......
Page 2: ......
Page 644: ...App 94 Appendix 6 External Dimensions Appendix 6 2 QJ71GP21S SX APPENDICES Memo ...
Page 649: ......
Page 650: ......