10.1 Troubleshooting Flow
10.1.8 Data link is disabled in the redundant system
10
- 11
9
DE
DICA
T
E
D
INS
T
RUCT
IONS
10
T
R
OUB
L
E
S
HO
OT
IN
G
APPENDI
CES
INDEX
10
TROUBLESHOOTING
(2) When no system switching occurs in Redundant CPUs even though the
cable of the CC-Link IE controller network module is disconnected
The following flowchart shows the procedures to be taken when no system switching
occurs in Redundant CPUs even if the cable of the CC-Link IE controller network
module is disconnected.
Figure 10.10 When no system switching occurs in Redundant CPUs even if the cable of the CC-Link IE controller network module
is disconnected
Is the POWER LED on the
standby system power supply
module on?
On
Off
No
Has a stop error occurred
in the standby system CPU?
Yes
No
Has an error occurred
in the standby system
CC-Link IE controller
network module?
Yes
No
Is the tracking cable
disconnected?
Connect the tracking cable properly.
Yes
Refer to the troubleshooting section in the following
manual.
QnPRHCPU User's Manual
(Redundant System)
OFF (Enable)
Data-link-error-induced
system switching disable flag
(SB0017)
ON
(Disable)
End
QCPU User's Manual
(Hardware Design, Maintenance and
Inspection)
QCPU User's Manual
(Hardware Design, Maintenance
and Inspection)
Check the error details and take corrective actions.
Check the error details and take corrective actions.
No system switching occurs in Redundant
CPUs even though the CC-Link IE controller
network module cable is disconnected.
Supply power.
The power supply module hardware may be faulty.
Please consult your local Mitsubishi
representative, explaining a detailed description of
the problem.
Review the system configuration so that the total
current does not exceed the rated output current
of the power supply module.
Even if a data link error is detected, no system
switching request will be issued to the control
system CPU.
Set the Data-link-error-induced system switching
disable flag (SB0017) to OFF.
Summary of Contents for QJ71GP21-SX
Page 1: ......
Page 2: ......
Page 644: ...App 94 Appendix 6 External Dimensions Appendix 6 2 QJ71GP21S SX APPENDICES Memo ...
Page 649: ......
Page 650: ......