2) When failed
(3) Error
When a link dedicated instruction failed, the error details can be confirmed by either of
the following methods.
(a) Using GX Developer
The error details can be checked in the CC IE Control Network Diagnostics.
(
Section 10.3 CC IE Control Network Diagnostics)
(b) Checking devices
Completion status indication device ((D1)+1) is turned ON, and an error code is
stored in Send/receive instruction processing result (SW0030 to SW0037).
Check the error and take corrective actions according to the error code.
(
Figure 9.114 When the RRUN instruction failed
Table 9.75 Send/receive instruction processing result
No.
Name
SW0030
Send/receive instruction (1) processing result
SW0031
Send/receive instruction (2) processing result
SW0032
Send/receive instruction (3) processing result
SW0033
Send/receive instruction (4) processing result
SW0034
Send/receive instruction (5) processing result
SW0035
Send/receive instruction (6) processing result
SW0036
Send/receive instruction (7) processing result
SW0037
Send/receive instruction (8) processing result
1 scan
RRUN
Sequence scan
Start contact
Own station CPU
CC-Link IE controller
network module
Completion device
(Device specified in (D1))
Completion status indication
device (Device of (D1)+1)
Error code
Send/receive instruction (1)
processing result (SW0030)
END
0
END
0
Channel 1
Target station error
END
0
END
0
END
0