10 - 24 10 - 24
MELSEC-Q
10 DEDICATED INSTRUCTIONS
(4) Whether a CPRTCL instruction was completed normally or abnormally can be
checked by the completion device ((D)) or status display device at completion
((D)+1).
(a) Completion device: Turns ON at the END processing of the scan where the
CPRTCL instruction is completed, and turns OFF at the
next END processing.
(b) Status display device
at completion : Turns ON and off depending on the completion status of
the CPRTCL instruction.
y
Normal completion : OFF with no change.
y
Error completion : Turns ON at the END
processing of the scan where
the CPRTCL instruction is
completed, and turns OFF at
the next END processing.
ON
ON
OFF
OFF
END
END
END
END
[Operation during execution of the CPRTCL instruction]
Sequence program
CPRTCL instruction
Completion device
Execution of
CPRTCL instruction
Completion of
sending by
CPRTCL instruction
Error
completion
Normal
completion
One scan
Status display device
at completion
POINT
The following describes how to check the execution status of protocols.
(1) Checking with the buffer memory
Use the protocol execution status (address: 4041
H
/4051
H
).
For details, refer to Section 3.9.
(2) Checking with state monitor
Open the "Predefined Protocol Function" tab in the "State Monitor" screen.
For details, refer to Operating Manual (Pre-defined protocol support function).
Summary of Contents for MELSEC QJ71C24
Page 1: ......
Page 2: ......
Page 103: ...3 42 3 42 MELSEC Q 3 SPECIFICATIONS MEMO ...
Page 177: ...6 33 6 33 MELSEC Q 6 DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL MEMO ...
Page 397: ...App 24 App 24 MELSEC Q APPENDIXES Connection example 3 Connection example 4 ...
Page 441: ......
Page 442: ......