App. - 51 App. - 51
MELSEC-Q
APPENDIXES
Appendix 9.8 When performing initial setting
The following program example performs initial setting using the REMTO instruction.
Execute this program when changing the default values of the Q series C24 buffer
memory.
Refer to Chapter 8 when changing the default values of the Q series C24 buffer
memory using GX Configurator-SC.
(1) Program conditions
The following program performs initial setting on the CH1 side when the initial
setting command (X1027) turns ON.
(a) Devices used
:
• Initial setting command ........................................................... X1027
• Initial setting command pulse signal....................................... M10
• Initial setting command 2 ........................................................ M11
• Initial setting command 3 ........................................................ M12
• Completion device for REMTO instruction ............................. M100 to105
• Normal/abnormal completion flag for REMTO instruction ..... M200 to 203
• Word/byte units designation.................................................... D0
• Buffer memory head address designation for on-demand
function.................................................................................... D1
• Buffer memory length designation for on-demand
function.................................................................................... D2
• Transmission buffer memory head address designation....... D3
• Transmission buffer memory length designation ................... D4
• Receive buffer memory head address designation................ D5
• Receive buffer memory length designation ............................ D6
(b) Buffer memory settings used in this example
Address Decimal (Hexadecimal)
CH1
Name
Setting
value
150 (96
H
)
Word/byte units designation
Byte units
160 (A0
H
)
Buffer memory head address designation for on-demand function
designation
0400
H
161 (A1
H
)
Data length designation for on-demand function designation
0000
H
162 (B2
H
)
Transmission buffer memory head address designation
0C00
H
163 (A3
H
)
Transmission buffer memory length designation
0400
H
166 (A6
H
)
Receive buffer memory head address designation
0600
H
167 (A7
H
)
Receive buffer memory length designation
0200
H
Summary of Contents for MELSEC QJ71C24
Page 1: ......
Page 2: ......
Page 103: ...3 42 3 42 MELSEC Q 3 SPECIFICATIONS MEMO ...
Page 177: ...6 33 6 33 MELSEC Q 6 DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL MEMO ...
Page 397: ...App 24 App 24 MELSEC Q APPENDIXES Connection example 3 Connection example 4 ...
Page 441: ......
Page 442: ......