10 - 6 10 - 6
MELSEC-Q
10 DEDICATED INSTRUCTIONS
Program example
A program that sends data stored in D10 to D11 using an on-demand transmission
When input/output signals of the Q series C24 are from X/Y00 to X/Y1F
On-demand transmission command pulse
Set the transmission channel to CH1.
Set the send data count to 2 words.
Set the transmission data to D10 to D11.
Reset the normal completion flag.
Set the transmission ready flag.
On-demand transmission execution
Normal completion
Reset the abnormal completion flag.
Abnormal completion
Reset the transmission ready flag.
POINT
(1) The status of communication via dedicated instructions can be read by an
SPBUSY instruction.
(2) Designate the storage capacity of transmission data (stored in D10 to D11 in
the program example above) and data length (stored in D2 in the program
example above) within the range of the buffer memory the user has assigned
for an on-demand function.
Summary of Contents for MELSEC QJ71C24
Page 1: ......
Page 2: ......
Page 103: ...3 42 3 42 MELSEC Q 3 SPECIFICATIONS MEMO ...
Page 177: ...6 33 6 33 MELSEC Q 6 DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL MEMO ...
Page 397: ...App 24 App 24 MELSEC Q APPENDIXES Connection example 3 Connection example 4 ...
Page 441: ......
Page 442: ......