9 - 47 9 - 47
MELSEC-Q
9 UTILITY PACKAGE (GX Configurator-SC)
9.6.6 Bidirectional monitor
[Purpose]
Monitor the status and setting values of the data transmission using the
bidirectional protocol.
[Operating procedure]
[Monitor] screen CH Bidirectional monitor
[Monitor screen]
[Monitor items]
Buffer memory address
Item
CH1 CH2
Reference section
Data transmission result
257
H
267
H
Data reception result
258
H
268
H
Chapter 11
X00: CH1 Transmission normal completion/
X07: CH2 Transmission normal completion
X01: CH1 Transmission abnormal completion/
X08: CH2 Transmission abnormal completion
X02: CH1 Transmission processing in progress/
X09: CH2 Transmission processing in progress
X03: CH1 Reception data read request/
X0A: CH2 Reception data read request
Y00: CH1 Transmission request/
Y07: CH2 Transmission request
Y01: CH1 Reception data read completion/
Y08: CH2 Reception data read completion
— —
Chapter
7
Simultaneously transmission data valid/invalid designation
9B
H
13B
H
Section
7.3