3 - 8 3 - 8
MELSEC-Q
3 SPECIFICATIONS
3.3.2 RS-422/485 cable specifications
The following shows the RS-422/485 cable specification.
(1) Use a 1200 m (3937 ft.), or shorter, cable that satisfies the following specification
for the RS-422/485 cable (cable to connect the Q series C24 terminal block).
Item Description
Cable type
Shielded cable
Number of pairs
3P
Conductor resistance (20
°
C)
88.0
/km or less
Insulation resistance
10000 M
- km or more
Dielectric strength
500 V DC, 1 minute
Electrostatic capacitance (1 kHz)
60nF/km or less on average
Characteristic impedance (100 kHz)
110 ± 10
Recommended conductor size
0.2 mm
2
to 0.75 mm
2
Diameter
AWG22 to AWG16
Type Stranded
wire
Material Copper
wire
Temperature rating
60
°
C or more
(Recommended cable)
SPEV (SB)-MPC-0.2 3P ..... (MITSUBISHI CABLE INDUSTRIES, Ltd.)
SPEV (SB)-0.2 3P .............. (MITSUBISHI CABLE INDUSTRIES, Ltd.)
SPEV (SB)-MPC-0.2 3P and SPEV (SB)-0.2 3P have the same electrical
characteristics, but different external diameter and internal wire colors.
(2) Make the total distance within 1200 m (3937 ft.) when two or more device are
connected in a 1:n or m:n configuration.