MELSEC-Q
4 SETTINGS AND PROCEDURES PRIOR TO OPERATION
4.5.2 Switch settings for I/O and intelligent functional module
[Setting purpose]
In the switch setting for I/O modules and intelligent functional modules, set the
transmission specifications and communication protocols for communication with
external devices.
[Setting procedure]
[PLC parameters] [I/O assignment setting] Switch setting .
For screen display, see the GX Developer Operating Manual.
[Setting screen]
[Display description]
(1) Switches 1 to 5
Set the transmission specifications and communication protocol of each interface
using the combinations of setting values for each switch with 16 bit binary data
according to the following table.
Switch number
Description
Remarks
b15 to b8
b7 to b0
Switch 1
CH1 Communication rate setting
CH1 Transmission setting
See a) and b)
Switch 2
CH1 communication protocol setting
See c)
b15 to b8
b7 to b0
Switch 3
CH2 Communication rate setting
CH2 Transmission setting
See a) and b)
Switch 4
CH2 Communication protocol setting
See c)
Switch 5
Station number setting
See d)
For settings to perform linked operation between two Q series C24 interfaces, see (2).
POINT
• When GX Developer or a GOT is connected to the Q series C24 on a 1:1 (one-to-
one) basis:
The switch setting in GX Developer is not required for accessing or monitoring a
QCPU. (If the switches are not set, the GX Developer connection mode will be
active.)
• When GX Developer or a GOT is connected to the Q series C24 on a 1:n (multi-
drop) basis:
Refer to the GX Developer Operating Manual.
Summary of Contents for MELSEC QJ71C24
Page 1: ......
Page 2: ......
Page 103: ...3 42 3 42 MELSEC Q 3 SPECIFICATIONS MEMO ...
Page 177: ...6 33 6 33 MELSEC Q 6 DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL MEMO ...
Page 397: ...App 24 App 24 MELSEC Q APPENDIXES Connection example 3 Connection example 4 ...
Page 441: ......
Page 442: ......