6 - 23 6 - 23
MELSEC-Q
6 DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL
6.2 Sending Data to the External Device
This section explains data transmission from the programmable controller CPU to the
external device.
6.2.1 Transmission methods
The following shows how to send data in any format using the non procedure protocol.
Transmission area
(buffer memory)
STX
A
B
C
D
E
F
G
H
ETX
Transmission data
(02
H
) (41
H
)
(48
H
)
(47
H
)
(46
H
)
(45
H
)
(44
H
)
(43
H
)
(42
H
)
(03
H
)
A
(41
H
)
G
(47
H
)
E
(45
H
)
C
(43
H
)
STX
B
D
F
H
(02
H
)
(48
H
)
(46
H
)
(44
H
)
(42
H
)
ETX
(03
H
)
10
(0A
H
)
(00
H
)
3)
Transmission data
ETX
H
(03
H
)
(48
H
)
(41
H
)
(03
H
)
External device
A
STX
1) 2)
OUTPUT instruction
Q series C24
Transmission
data count
Transmission
data
Programmable controller CPU
OUTPUT instruction
completion device
OUTPUT instruction
OUTPUT
Transmission instruction
Contents
CH1/CH2
Control timing
1) Transmission data is stored in the device designated with the OUTPUT instruction.
2) Control data is stored in the device designated with the OUTPUT instruction.
3) When the OUTPUT instruction is executed, the Q series C24 sends the amount of
data designated by the transmission data count from the transmission data area to
the external device in ascending order of the transmission data area addresses.
Summary of Contents for MELSEC QJ71C24
Page 1: ......
Page 2: ......
Page 103: ...3 42 3 42 MELSEC Q 3 SPECIFICATIONS MEMO ...
Page 177: ...6 33 6 33 MELSEC Q 6 DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL MEMO ...
Page 397: ...App 24 App 24 MELSEC Q APPENDIXES Connection example 3 Connection example 4 ...
Page 441: ......
Page 442: ......