11 - 22 11 - 22
MELSEC-Q
11 TROUBLESHOOTING
Protocol
Error code
(Hexa-
decimal)
Error
Description
Signal
name
Corrective action
MC
Non
Proce-
dure
Bidire-
ctional
Pre-
defined
7D19
H
Invalid number of
digits error
•
When data are received by the protocol
including a packet that contains a
conversion variable (variable number of
data and variable number of digits), the
corresponding data is 0 bytes (0 digits)
or exceeds the maximum number of
digits.
CHn
ERR.
•
Correct the data sent from the device.
•
If the protocol was edited in GX
Configurator-SC (Pre-defined protocol
support function), check the packet
format of the external device to see if
the number of digits is set correctly.
7D1A
H
Data length error
•
In the data received from the external
device, the Length value does not
match the data length of the conversion
variable(s).
CHn
ERR.
•
Check the data sent from the external
device to see if:
(1) The Length value is correct or not.
(2) Any of the data corresponding to the
conversion variable is missing or
not.
•
If GX Configurator-SC (Pre-defined
protocol support function) was used for
protocol editing, check the sender’s
packet format to see if an incorrect
value is set for the conversion variable.
7D1B
H
Value range error
•
When the protocol used for data
reception includes a packet that
contains a conversion variable, a value
of the data for the conversion variable
exceeds the range allowed for the Q
series C24N.
CHn
ERR.
•
Check the data sent from the external
device.
•
If GX Configurator-SC (Pre-defined
protocol support function) was used for
protocol editing, check the sender’s
packet format to see if an incorrect
value is set for the conversion size.
(1) If it exceeds the range for word data,
change the conversion size setting to
Double word.
(2) If it exceeds the range for double-word
data, change the element to Non-
conversion variable.
7D20
H
Data length setting
error, data quantity
setting error
•
The value set in the data length storage
area or the data quantity storage area is
out of range.
CHn
ERR.
•
Check the maximum allowable data
length, and specify the maximum length
or less in the data length storage area.
•
Check the maximum allowable data
quantity, and specify the maximum
quantity or less in the data quantity
storage area.
7D21
H
Decimal point
position error
•
An out-of-range value is set for the
decimal point position when the number
of decimals is set to Variable.
•
The number of decimals is larger than
the number of digits for each data.
CHn
ERR.
•
Correct the value set for the decimal
point position.
•
Check the number of digits setting, and
set the decimal point position so that
the number of decimals is less than the
number of digits.
7E00
H
to
7E05
H
System error
•
The OS of the Q series C24 detected
some error.
⎯
(
1)
7E06
H
Buffer memory
address setting error
•
Transmit/receive buffer memory
addresses are in the special
applications area.
⎯
•
Change the buffer memory addresses so
that they are outside the special
applications area.
7E07
H
System
error
•
The OS of the Q series C24 detected
some error.
⎯
(
1)
7E08
H
Currently
inexecutable error
•
The UINI instruction was executed
during programmable controller CPU
information clear.
⎯
•
Execute the UINI instruction while the
programmable controller CPU
information clear is not executed.
7E09
H
7E0A
H
System error
•
The OS of the Q series C24 detected
some error.
⎯
(
1)
7E40
H
Command
error
•
A nonexistent command or
subcommand was designated.
PRO
•
Check and correct the external device
transmit message and restart data
communications.
7E41
H
Data length error
•
A data length exceeding the number of
points that can communicate during
random read/write was designated.
PRO
•
Check and correct the external device
transmit message and restart data
communications.
Summary of Contents for MELSEC QJ71C24
Page 1: ......
Page 2: ......
Page 103: ...3 42 3 42 MELSEC Q 3 SPECIFICATIONS MEMO ...
Page 177: ...6 33 6 33 MELSEC Q 6 DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL MEMO ...
Page 397: ...App 24 App 24 MELSEC Q APPENDIXES Connection example 3 Connection example 4 ...
Page 441: ......
Page 442: ......