11 - 44 11 - 44
MELSEC-Q
11 TROUBLESHOOTING
11.3.10 Communication error "PRO."
Symptom Cause
Corrective
action
MC
B
idi
rec
tional
Non
proc
edure
P
re-def
ined
• Communications were
performed with a control
procedure different from the
Q series C24 communication
protocol setting.
• Some of the data are
different from the control
procedure.
• Designated command does
not exist.
• The device No. designation
is not the character count
corresponding to the
command.
• Check the Q series C24 communication protocol
setting and the message from the external device
and match the settings, or correct the message and
restart data communications.
• Use the communication monitoring function to check
the message from the external device.
• The characters in the
message include a data other
than the "A to Z", "0 to 9",
"
", and control data.
• Check and correct the external device message and
restart data communications.
• Use the communication monitoring function to check
the message from the external device.
Note
• Only the data "0 to 9" and "A to F" can be handled
as character area data during communications
using an MC protocol (ASCII mode). Therefore,
when transmitting a character string as data,
convert the ASCII code of each character string to
2-byte binary code.
Examples)
• Transmitting the character "G"
The ASCII code for the character "G" is 47
H
and is
transmitted as the two bytes 34
H
, 37
H
.
• Transmitting the character "A"
The ASCII code for "A" is 41
H
and is transmitted as
the two bytes 34
H
, 31
H
.
If the ASCII code 41
H
for the character
"A" is transmitted unchanged, the Q series
C24 ASCII-BIN conversion will convert it to
A
H
(10) and pass it to the programmable
controller CPU.
• A device No. outside the
designated range was
designated.
• When designating a device, check "Device setting"
of the parameters written to the CPU and correct it to
a device No. within the designated range and restart
data communications.
• Communication error
signal "PRO" turned on.
• A remote RUN/STOP
request was issued while
remote STOP was applied
from another module.
• Check if remote STOP is applied from another
module and restart data communications.
Summary of Contents for MELSEC QJ71C24
Page 1: ......
Page 2: ......
Page 103: ...3 42 3 42 MELSEC Q 3 SPECIFICATIONS MEMO ...
Page 177: ...6 33 6 33 MELSEC Q 6 DATA COMMUNICATION USING THE NON PROCEDURE PROTOCOL MEMO ...
Page 397: ...App 24 App 24 MELSEC Q APPENDIXES Connection example 3 Connection example 4 ...
Page 441: ......
Page 442: ......