App. - 37 App. - 37
MELSEC-Q
APPENDIXES
Appendix 9 Program Examples for Using Q Series C24 at MELSECNET/H Remote I/O
Station
Appendix 9.1 System configuration and program conditions
(1) System configuration
The system configuration used in the program examples of this section is shown
below.
GX Developer
MELSECNET/H (remote I/O net)
network No.1
QJ71LP21-25
Remote master station
( 2)
Control target
QJ71C24N( 1)
QJ72LP25-25
Remote I/O station
(Station No.1)
1 It is assumed that the QJ71C24N is mounted on Slot 0 of the base unit and
the starting I/O No. is "0".
2 Set the network parameters of the remote master station as shown below.
1) Network type
: MNET/H (Remote master)
2) Starting I/O No.
: 0000
H
3) Network No.
: 1
4) Total stations
: 1
5) Mode
: Online
6) Network range assignment (XY setting)
7) Refresh parameters