16 FX2N-8/16E*-*(Input/Output Extension Blocks)
16.8 FX2N-8EYR-ES/UL, FX2N-8EYR-S-ES/UL, FX2N-16EYR-ES/UL (Relay Output)
16.8
FX
2N
-8EYR-ES/UL, FX
2N
-8EYR-S-ES/UL, FX
2N
-16EYR-ES/UL
(Relay Output)
16.8.1 Product specifications
The generic specifications are identical to the main unit specifications.
→
Refer to Section 4.1 for generic specifications.
For external wiring, refer to the following chapter.
→
Refer to Chapter 12 for output wiring.
1. Power supply specifications
2. Weight and Other specifications
3. Output specifications (Relay output type)
Item
FX
2N
-8EYR-ES/UL
FX
2N
-16EYR-ES/UL
FX
2N
-8EYR-S-ES/UL
Product type
FX
2N
extension block
Rated voltage
24V DC (supplied from main unit and input/output powered extension unit)
Item
FX
2N
-8EYR-ES/UL
FX
2N
-16EYR-ES/UL
FX
2N
-8EYR-S-ES/UL
MASS (Weight)
0.2 kg (0.44lbs)
0.3 kg (0.66lbs)
Others
• The extension cable is already connected to the extension block.
• Accessories: Label for indication of input/output number
• The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
Item
FX
2N
-8EYR-ES/UL
FX
2N
-16EYR-ES/UL
FX
2N
-8EYR-S-ES/UL
Output points
8 points
16 points
8 points
(All points have separate reference
terminals (commons))
Connection unit
Vertical terminal block (M3 screws)
Output unit
Relay
External power supply
30V DC or less
240V AC or less
(250V AC or less when the unit does not comply with CE, UL, or cUL standards)
Output circuit insulation method
Mechanical insulation
Indication of output operation
Supplying power to the relay coil will light the LED indicator lamp on panel.
Maximum load
Resistance
load
2 A/point
The total resistance load current per common
should be as follows:
• 4 output points/common: 8A or less
• 8 output points/common: 8A or less
2 A/point
Inductive
load
80 VA
→
For the product life, refer to Subsection 4.4.2.
→
For cautions on external wiring, refer to Subsection 12.2.4.
Open circuit leakage current
−
Minimum load
5V DC, 2 mA (reference values)
Response time
OFF
→
ON
Approx. 10 ms
ON
→
OFF
Approx. 10 ms
Output circuit diagram
A common number applies to the
of [COM
].
Load
DC power
supply unit
Fuse
Y
AC power
supply unit
Fuse
Y
COM
COM
Load
DC power
supply unit
Fuse
Y0
AC power
supply unit
Fuse
Y0
Y7
Y7