FX
3U
Series Programmable Controllers
User’s Manual - Hardware Edition
346
16 FX2N-8/16E*-*(Input/Output Extension Blocks)
16.11 FX2N-8EYT, FX2N-16EYT and FX2N-16EYT-C (Transistor Output)
16.11 FX
2N
-8EYT, FX
2N
-16EYT and FX
2N
-16EYT-C (Transistor Output)
16.11.1 Product specifications
The generic specifications are identical to the main unit specifications.
→
Refer to Section 4.1 for generic specifications.
For external wiring, refer to the following chapter.
→
Refer to Chapter 12 for output wiring.
1. Power supply specifications
2. Weight and Other spesifications
3. Output specifications (Transistor output type)
Item
FX
2N
-8EYT
FX
2N
-16EYT
FX
2N
-16EYT-C
Product type
FX
2N
extension block
FX
2N
connector type extension block
Rated voltage
24V DC (supplied from main unit and input/output powered extension unit)
Item
FX
2N
-8EYT
FX
2N
-16EYT
FX
2N
-16EYT-C
MASS (Weight)
0.2 kg (0.44lbs)
0.3 kg (0.66lbs)
Other
• The extension cable is already connected to the extension block.
• Accessories: Label for indication of input/output number
• The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
Item
FX
2N
-8EYT
FX
2N
-16EYT
FX
2N
-16EYT-C
Output points
8 points
16 points
Connection unit
Vertical terminal block (M3 screws)
Connector terminal block
Output unit/type
Transistor/sink output
External power supply
5 to 30V DC
Output circuit insulation method
Photo-coupler insulation
Indication of output operation
Activation of the photo-coupler will light the LED indicator lamp on panel.
Maximum load
Resistance
load
0.5 A/point
The total load current per common
should be as follows:
• 4 output points/common: 0.8A or less
• 8 output points/common: 1.6A or less
0.3 A/point
The total load current per common
should be as follows:
• 16 output points/common: 1.6A or
less
Inductive load
12 W/24V DC
7.2 W/24V DC
Open circuit leakage current
0.1 mA/30 A DC
Minimum load
−
Response time
OFF
→
ON
0.2 ms or less for 200 mA (at 24V DC)
ON
→
OFF
0.2 ms or less for 200 mA (at 24V DC)
Output circuit diagram
Load
Fuse
DC power
supply unit
Fuse
DC power
supply unit
Y
COM1
Y
COM2
Load
Fuse
DC power
supply unit
Y
COM
Fuse
DC power
supply unit
Y
COM
Summary of Contents for FX2-16E series
Page 2: ......
Page 8: ... 6 Safety Precautions Read these precautions before use MEMO ...
Page 519: ......