10 Input Wiring Procedures (Input Interruption and Pulse Catch)
10.2 24V DC Input Type (Common to Sink/Source Input)
1
Introducti
on
2
Features
and
Par
t Names
3
Product
Introduc
tion
4
Sp
eci
fic
ati
ons
5
V
ers
ion and
Peri
ph
er
al
D
evices
6
S
yst
em
C
onfi
guration
7
Input/Ou
tput
No
s., Un
it No
s.
8
Inst
allati
on
9
Prep
arati
on an
d
Pow
er Supp
ly
Wi
rin
g
10
Input W
iring
Cautions on wiring when changing filter time
When setting the input filter to 5
µ
s or capturing pulses of a response frequency of 50 to 100kHz with a high-
speed counter, wire the terminals as stated below.
1) The wiring length should be 5m or less.
2) Connect a bleeder resistance of 1.5k
Ω
(1 W or more) to the input terminal, so that the sum of the load
current of the open collector transistor output on the mating device and the input current of the main body
is 20 mA or more.
3. Input sensitivity
The PLC input current and input sensitivity are shown in the following table.
When there is a series diode or resistance at the input contact or there is a parallel resistance or leakage
current at the input contact, wire the terminals according to the following table.
→
For the instructions for connecting input devices, refer to Subsection 10.2.3.
4. Examples of input wiring
For the wiring of input interruption, pulse catch and rotary encoder, refer to the following sections.
→
Example of wiring of input interruption: Refer to Section 10.4.
→
Example of wiring of pulse catch: Refer to Section 10.5.
→
Example of wiring of rotary encoder: Refer to Section 11.10.
10.2.3 Instructions for connecting input devices
1. In case of no-voltage contact
The input current of this PLC is 5 to 7 mA/24V DC.
Use input devices applicable to this minute current.
If no-voltage contacts (switches) for large current are used, contact failure may occur.
<Example> Products of OMRON
2. In case of input device with built-in series diode
The voltage drop of the series diode should be approx. 4V or less.
When lead switches with a series LED are used, up to two switches can be connected in series.
Also make sure that the input current is over the input-sensing level while the switches are ON.
Item
X000 to X005
X006 to X007
X010 to max input number
of the main unit
Input voltage
AC power type: 24V DC
±
10% DC power type: 16.8 to 28.8V DC
Input current
6 mA
7 mA
5 mA
Input sensitivity
current
ON
3.5 mA or more
4.5 mA or more
3.5 mA or more
OFF
1.5 mA or less
1.5 mA or less
1.5 mA or less
Input number
Input current
X000 to X005
6 mA/24V DC
X006, X007
7 mA/24V DC
X010 or more
5 mA/24V DC
Type
Model name
Type
Model name
Microswitch
Models Z, V and D2RV
Operation switch
Model A3P
Proximity switch
Model TL
Photoelectric switch
Model E3S
PLC
(source input)
X
24V
LED
*1 In case of a type only for sink input,
connect the device to the COM terminal.
PLC
(sink input)
X
0V
LED
*1
24V
S/S
S/S
0V