FX
3U
Series Programmable Controllers
User’s Manual - Hardware Edition
352
16 FX2N-8/16E*-*(Input/Output Extension Blocks)
16.13 FX2N-16EYS (Triac Output: 16 Points)
16.13 FX
2N
-16EYS (Triac Output: 16 Points)
16.13.1 Product specifications
The generic specifications are identical to the main unit specifications.
→
Refer to Section 4.1 for generic specifications.
For external wiring, refer to the following chapter.
→
Refer to Chapter 12 for output wiring.
1. Power supply specifications
2. Weight and Other specifications
3. Output specifications (Triac output type)
Item
FX
2N
-16EYS
Product type
FX
2N
extension block
Rated voltage
24V DC (supplied from main unit and input/output powered extension unit)
Item
FX
2N
-16EYS
MASS (Weight)
0.3 kg (0.66lbs)
Other
• The extension cable is already connected to the extension block.
• Accessories: Label for indication of input/output number
• The DIN46277 rail (width: 35 mm (1.38")) or direct installation.
Item
FX
2N
-16EYS
Output points
16 points
Connection unit
Vertical terminal block (M3 screws)
Output unit
Triac output (SSR)
External power supply
85 to 242V AC
Output circuit insulation method
Photo-coupler insulation
Indication of output operation
Activation of the photo-thyristor will light the LED indicator lamp on panel.
Maximum load
Resistance
load
0.3 A/point
The total load current per common should be as follows:
• 8 output points/common: 0.8A or less
Inductive load
15 VA/100V AC, 30 VA/200V AC
Open circuit leakage current
1 mA/100V AC, 2 mA/200V AC
Minimum load
0.4 VA/100V AC, 1.6 VA/200V AC
Response time
OFF
→
ON
1 ms or less
ON
→
OFF
10 ms or less
Output circuit diagram
A common number applies to the of [COM ].
U
Load
Fuse
Y
COM
AC power
supply
Summary of Contents for FX2-16E series
Page 2: ......
Page 8: ... 6 Safety Precautions Read these precautions before use MEMO ...
Page 519: ......