52
4 Specifications, External Dimensions and Terminal Layout (Main Units)
4.1 Generic Specifications
FX
3U
Series Programmable Controllers
User’s Manual - Hardware Edition
4.
Specifications, External Dimensions and Terminal
Layout (Main Units)
This Chapter explains the specifications, external dimensions and terminal layout of the main units.
→
For input/output powered extension unit specifications, refer to Chapter 15.
→
For input/output extension block specifications, refer to Chapter 16.
4.1
Generic Specifications
*1.
The criterion is shown in IEC61131-2.
*2.
Ground the PLC independently or jointly.
→
Refer to Section 9.4.
*3.
For more information on the dielectric withstand voltage test and the insulation resistance test of the
terminals of each product, refer to the following.
→
Refer to Subsection 4.1.1.
*4.
Do not use the PLC under pressure higher than the atmospheric pressure. Doing so may damage the
PLC.
Item
Specification
Ambient
temperature
0 to 55
°
C (32 to 131
°
F) when operating and -25 to 75
°
C (-13 to 167
°
F) when stored
Ambient
humidity
5 to 95%RH (no condensation) when operating
Vibration
resistance
*1
Frequency
(Hz)
Acceleration
(m/s
2
)
Half amplitude
(mm)
Sweep Count for X,
Y, Z: 10 times
(80 min in each
direction)
When installed on
DIN rail
10 to 57
−
0.035
57 to 150
4.9
−
When installed
directly
10 to 57
−
0.075
57 to 150
9.8
−
Shock
resistance
*1
147 m/s
2
Acceleration, Action time: 11ms, 3 times by half-sine pulse in each direction X, Y, and Z
Noise
resistance
By noise simulator at noise voltage of 1,000 Vp-p, noise width of 1
µ
s, rise time of 1 ns and period of
30 to 100 Hz
Dielectric
withstand
voltage
*3
1.5kV AC for one minute
Between each terminals
and ground terminal
500V AC for one minute
Insulation
resistance
*3
5M
Ω
or more by 500V DC megger
Grounding
Class D grounding (grounding resistance: 100
Ω
or less)
<Common grounding with a heavy electrical system is not allowed>
*2
Working
atmosphere
Free from corrosive or flammable gas and excessive conductive dust
Working
altitude
<2000m
*4
PLC
Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition
PLC
Other
equipment
PLC
Other
equipment