6 Examination of System Configuration
6.9 Example of System Configuration and System Modification
1
Introducti
on
2
Features
and
Par
t Names
3
Product
Introduc
tion
4
Sp
eci
fic
ati
ons
5
V
ers
ion and
Peri
ph
er
al
D
evices
6
S
yst
em
C
onfi
guration
7
Input/Ou
tput
No
s., Un
it No
s.
8
Inst
allati
on
9
Prep
arati
on an
d
Pow
er Supp
ly
Wi
rin
g
10
Input W
iring
6.9.2
Expansion of main unit
The suitability of the above system configuration is evaluated as shown below.
1
Enter the specifications for the main unit.
2
Enter the specifications for the products to be connected to the main unit.
*1.
The number for FX
2N
-64CL-M is calculated by adding the number of input/output points at the
connected remote I/O station to 8 points.
Classification
Number of
connected
units
Type
Number of
input/output
points [points]
Capacity of built-in power
supply
5V DC power
supply [mA]
24V DC service
power supply
[mA]
With built-in
power
supply
Main unit
1
FX
3U
-48MR/ES
48
500
600
Classification
Number of
connected
units
Type
Number of
input/output
(occupied)
points [points]
Calculation of current
consumption of built-in
power supply
5V DC power
supply [mA]
24V DC power
supply [mA]
Enter the
products
connected to
the main unit.
Expansion
board
1
FX
3U
-232-BD
−
20
0
Special adapter
6
FX
3U
-4HSX-ADP
−
30
30
FX
3U
-2HSY-ADP
−
30
60
FX
3U
-2HSY-ADP
−
30
60
FX
3U
-485ADP(-MB)
−
20
0
FX
3U
-4AD-ADP
−
15
0
FX
3U
-4AD-ADP
−
15
0
Input/output
extension block
4
FX
2N
-16EX-ES/UL
16
−
100
FX
2N
-16EYT-ESS/UL
16
−
150
FX
2N
-16EX-ES/UL
16
−
100
FX
2N
-16EYR-ES/UL
16
−
150
Special function
unit/block
6
FX
2N
-1HC
8
90
0
FX
2N
-10PG
8
120
0
FX
2N
-2LC
8
70
0
FX
2N
-64CL-M
8+16
*1
190
0
FX
2N
-16CCL-M
8
0
0
FX
2N
-32CCL
8
130
0
Calculate the totals.
128
760
650