10 Input Wiring Procedures (Input Interruption and Pulse Catch)
10.5 Pulse Catch (M8170 to M8177)
10.5
Pulse Catch (M8170 to M8177)
The PLC (main unit/DC input type) is provided with a pulse catch function and has 8 pulse catch input points.
→
For details on programming, refer to the programming manual.
10.5.1 Allocation of special memories to input numbers (ON duration of input signals)
10.5.2 Cautions for pulse catch
1. Non-overlap of input numbers
The input terminals X000 to X007 can be used for high-speed counter, input interruption, pulse catch, speed
detection (SPD) instructions and general-purpose input.
Take care not to overlap the input numbers.
Example:
When the pulse catch input contact M8170 is used, X000 is occupied. Therefore, it is impossible to use C235,
C241, C244, C246, C247, C249, C252 and C254, input interruption (including delay interruption) pointers
I000 and I001 and SPD, ZRN, DSZR and DVIT instructions at the same time.
2. Cautions on wiring
• The wiring length should be 5 m (16’4") or less.
• Connect a bleeder resistance of 1.5k
Ω
(1 W or more) to the input terminal, so that the sum of the load
current of the open collector transistor output on the other side device and the input current of the main
body is 20 mA or more.
Input No.
Contact on sequence program
ON duration of input signal
X000
M8170
5
µ
s or more
X001
M8171
X002
M8172
X003
M8173
X004
M8174
X005
M8175
X006
M8176
50
µ
s or more
X007
M8177