298
FX
3U
Series Programmable Controllers
User’s Manual - Hardware Edition
15 FX2N-32/48E*-* (Input/Output Powered Extension Units)
15.3 FX2N-32ER-ES/UL, FX2N-48ER-ES/UL, FX2N-48ER-DS
3. Output specifications (relay output type)
15.3.2 External dimensions
FX
2N
-32ER-ES/UL
Item
FX
2N
-32ER-ES/UL
FX
2N
-48ER-ES/UL, FX
2N
-48ER-DS
Number of output points
16 points
24 points
Connection type
Removable terminal block (M3 screw)
Output unit
Relay
External power supply
30V DC or less
240V AC or less (250V AC or less when the unit does not comply with CE, UL or
cUL standards)
Output circuit insulation
Mechanical insulation
Indication of output operation
When power is applied to relay coil, LED is lit.
Max. load
Resistance
load
2A/point
The total load current per common
terminal should be the following value.
• 4 output points/common terminal: 8 A
or less
2A/point
The total load current per common
terminal should be the following value.
• 4 output points/common terminal: 8 A
or less
• 8 output points/common terminal: 8 A
or less
Inductive load
80 VA
→
For the product life, refer to Subsection 4.4.2.
→
For cautions on external wiring, refer to Subsection 12.2.4.
Open circuit leakage current
−
Min. load
5V DC, 2 mA (reference value)
Response time
OFF
→
ON
Approx. 10 ms
ON
→
OFF
Approx. 10 ms
Output circuit diagram
External
power supply
Load
Fuse
Y
COM
DC power
supply
Fuse
Y
COM
A number (1 or more) is entered in of [COM ].
7
2
4 5 6
1
3
0
7
2
4 5 6
1
3
0
OUT
IN
L
X1
X3
X5
X7
X6
X0
X2
X4
X6
24V
N
0V
S/S
X4
X7
COM4
COM2
Y4
Y5
Y6
Y7
COM3
Y0
Y1
Y2
Y3
COM1
Y0
Y1
Y2
Y3
Y4
Y5
Y6
Y7
X3
X2
X1
X0
X5
FX
2N
-32ER
POWER
7
2
4 5 6
1
3
0
7
2
4 5 6
1
3
0
150 (5.91")
140 (5.52") (mounting hole pitch)
80 (3.15")
(mounting hole pitch)
90 (3.55")
9 (0.36")
Unit : mm (inches)
87 (3.43")
2-
φ
4.5 mounting holes
The terminal block uses
M3 terminal screws.
Summary of Contents for FX2-16E series
Page 2: ......
Page 8: ... 6 Safety Precautions Read these precautions before use MEMO ...
Page 519: ......