62
4 Specifications, External Dimensions and Terminal Layout (Main Units)
4.4 Output Specifications
FX
3U
Series Programmable Controllers
User’s Manual - Hardware Edition
4.4.5
Triac output type
Item
Triac output specifications
FX
3U
-32MS/ES
FX
3U
-64MS/ES
Number of output points
16 points
32 points
Connecting type
Removable terminal block (M3 screw)
Output type
Triac output (SSR)
External power supply
85 to 242V AC
Max. load
Resistance load
0.3 A / point
The total load current of resistance loads per common terminal should be the
following value.
→
For details on the common terminal for each model,
refer to the terminal block layout.
• 4 output points/common terminal: 0.8 A or less
• 8 output points/common terminal: 0.8 A or less
Inductive load
15VA/100V AC, 30VA/200V AC
Open circuit leakage current
1 mA/100V AC, 2 mA/200V AC
Min. load
0.4VA/100V AC, 1.6VA/200V AC
Response
time
OFF
→
ON
1 ms or less
ON
→
OFF
10 ms or less
Circuit insulation
Photo-thyristor insulation
Display of output operation
LED on panel lights when photo-thyristor is driven.
Output circuit configuration
Load
Fuse
External
power supply
Y
COM
A common number applies to the of [COM ].