[8-9 Troubleshooting Inverter Problems (TLMU) ]
- 269 -
HWE14080
GB
8
Tr
oubles
hoot
ing Ba
se
d
o
n
Obs
erv
ed Sympt
o
ms
8-9-8
Checking the Fan Inverter for Damage at No Load
Check list
Phenomenon
Resolution
(1)
Turn off breaker.
*Turn power off without fail.
1)
Within 30 seconds from the start of
operation, an error other than a posi-
tion error (5305, 5306) (detail code
132) is detected.
Change fan board.
(2)
Disconnect the connector
CNINV from the fan board.
2)
Less than 5V unbalance in the wiring. Change fan board.
(3)
Set fan board switch SW1-1 to
ON.
3)
No unbalanced voltage in the wiring.
After 30 second, detail code 132 is
produced and the system stops.
Normal
*After checking, return
SW1&CNINV.
(4)
Turn on breaker.
(5)
Operate unit.
After about 30 seconds under
no load with constant voltage
output, the code below will be
displayed indicating a position
error (5305, 5306).
Detail code: 132
Also, running with no load pro-
duces constant voltage of
about 160V.
Summary of Contents for R410A
Page 1: ......
Page 11: ... 2 HWE14080 GB ...
Page 25: ... 16 HWE14080 GB ...
Page 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Page 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Page 59: ... 50 HWE14080 GB ...
Page 71: ... 62 HWE14080 GB ...
Page 95: ... 86 HWE14080 GB ...
Page 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Page 123: ... 114 HWE14080 GB ...
Page 159: ... 150 HWE14080 GB ...
Page 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Page 309: ... 300 HWE14080 GB ...
Page 346: ......