[6-11 Standard Operation Data (Reference Data) ]
- 142 -
HWE14080
GB
6-11-3
Triple Unit Combination (Standard)
Packaged unit model
PUHY-P264T(Y)SLMU
Outdoor unit model
PUHY-P72T(Y)LMU
PUHY-P72T(Y)LMU
PUHY-P120T(Y)LMU
Conditions
Ambient temperature
(cooling)
Indoor
DB/WB
26.7°C/19.4°C
[80°F/67°F]
Outdoor
35°C/-
[95°F/-]
Ambient temperature
(heating)
Indoor
DB/WB
21.1°C/-
[70°F/-
Outdoor
8.3°C/6.1°C
[47°F/43°F]
Indoor unit
Number of units connected
Unit
7
Number of units in operation
7
Model
-
36/36/36/36/36/36/36
Piping
Main pipe
m [ft]
5
[16-3/8]
Branch pipe
10
[32-3/4]
Total pipe length
65
[213-1/4 ]
Fan speed
-
Hi
Refrigerant charge
kg [lbs-oz]
25
[55]
Outdoor unit
Voltage
*1
*1. Measurements of current and voltage that are listed in the table above are those of the TLMU model.
V
230
Cooling operation
Outdoor unit
Electric current
*1
A
64.1
Compressor frequency
Hz
52
52
74
LEV open-
ing
Indoor unit
Pulse
325/325/325/325/325/325/325
SC (LEV1)
190
190
100
LEV2
2100
2100
2100
Pressure
High pressure (after O/S)/Low pressure (before accumulator)
MPa [psi]
2.71/0.90
2.71/0.90
2.92/0.90
[393/131]
[393/131]
[424/131]
Section
tempera-
tures
Outdoor unit
Discharge (TH4)
°C [°F]
69
[156]
69
[156]
73
[163]
Heat exchanger outlet (TH3)
44
[111]
44
[111]
40
[104]
Accumulator inlet
10
[50]
10
[50]
10
[50]
Accumulator outlet
10
[50]
10
[50]
10
[50]
SCC outlet (TH6)
24
[75]
24
[75]
20
[68]
Compressor inlet
17
[63]
17
[63]
15
[59]
Compressor shell bottom
47
[117]
47
[117]
42
[108]
Indoor unit
LEV inlet
24
[75]
24
[75]
19
[66]
Heat exchanger outlet
10
[50]
10
[50]
10
[50]
Heating operation
Outdoor unit
Electric current
*1
A
67.4
Compressor frequency
Hz
53
53
81
LEV open-
ing
Indoor unit
Pulse
332/332/332/332/332/332/332
SC (LEV1)
0
0
0
LEV2
2100
2100
2100
Pressure
High pressure (after O/S)/Low pressure (before accumulator)
MPa [psi]
2.66/0.66
2.66/0.66
2.72/0.63
[387/95]
[387/95]
[395/91]
Section
tempera-
tures
Outdoor unit
Discharge (TH4)
°C [°F]
72
[162] 72
[162] 70
[158]
Heat exchanger outlet (TH3)
0
[32]
0
[32]
-1
[30]
Accumulator inlet
0
[32]
0
[32]
-1
[30]
Accumulator outlet
0
[32]
0
[32]
-1
[30]
Compressor inlet
0
[32]
0
[32]
-1
[30]
Compressor shell bottom
40
[104]
40
[104]
40
[104]
Indoor unit
LEV inlet
36
[97]
36
[97]
37
[98]
Heat exchanger inlet
69
[157]
69
[157]
75
[166]
Summary of Contents for R410A
Page 1: ......
Page 11: ... 2 HWE14080 GB ...
Page 25: ... 16 HWE14080 GB ...
Page 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Page 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Page 59: ... 50 HWE14080 GB ...
Page 71: ... 62 HWE14080 GB ...
Page 95: ... 86 HWE14080 GB ...
Page 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Page 123: ... 114 HWE14080 GB ...
Page 159: ... 150 HWE14080 GB ...
Page 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Page 309: ... 300 HWE14080 GB ...
Page 346: ......