[7-8 Error Code Definitions and Solutions: Codes [7000 - 7999] ]
- 232 -
HWE14080
GB
7-8-9
Error Code [7117]
1. Error
code
definition
Model setting error
2. Error source, cause, check method and remedy
Error source
Cause
Check method and remedy
Outdoor unit
(1)
Wiring fault
(Detail code 15)
(2)
Loose connectors, short-circuit, con-
tact failure
1)
Check the connector CNTYP5 on the control board for
proper connection.
(Detail code 12)
1)
Check the connector CNTYP2 on the control board for
proper connection.
2)
Check the connector CNTYP5 on the control board for
proper connection.
(Detail code 16)
1)
Check the connector CNTYP on the INV board for
proper connection.
2)
Check the connector CNTYP5 on the control board for
proper connection.
3)
Check the wiring between the control board and INV
board.
Refer to the following page(s). [7-2-1 Error Code
[0403]](page 156)
(Detail code 0, 1, 5, 6)
1)
Check the wiring between the control board and INV
board.
Refer to the following page(s). [7-2-1 Error Code
[0403]](page 156)
2)
Check the settings of SW5-3 through SW5-6 on the
control board.
3)
Check the connector CNTYP5 on the control board for
proper connection.
(Detail code Miscellaneous)
*If a set-model-name identification error occurs, check
the detail code on the unit on which the error occurred.
The detail code that appears on other units will be dif-
ferent from the ones shown above.
Summary of Contents for R410A
Page 1: ......
Page 11: ... 2 HWE14080 GB ...
Page 25: ... 16 HWE14080 GB ...
Page 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Page 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Page 59: ... 50 HWE14080 GB ...
Page 71: ... 62 HWE14080 GB ...
Page 95: ... 86 HWE14080 GB ...
Page 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Page 123: ... 114 HWE14080 GB ...
Page 159: ... 150 HWE14080 GB ...
Page 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Page 309: ... 300 HWE14080 GB ...
Page 346: ......