[7-6 Error Code Definitions and Solutions: Codes [5000 - 5999] ]
- 198 -
HWE14080
GB
7-6-10
Error Code [5301] Detail Code 118 (TLMU)
1. Error
code
definition
(P168 model only)
DCCT sensor circuit fault (Detail code118)
2. Error definition and error detection method
When an error value is detected with the DCCT detection circuit just before the inverter starts
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems (TLMU)](page 264)
Cause
Check method and remedy
(1)
Contact failure
Check for good contact of the INV board connector CNCT and the connector on the
DCCT side.
(2)
INV board failure
Refer to the following page(s).
[8-9-2 Checking the Inverter Board Error Detection Circuit](page 266)
[8-9-4 Checking the Inverter for Damage at No-Load](page 267)
[8-9-5 Checking the Inverter for Damage during Compressor Operation](page 268)
(3)
DCCT sensor failure
Replace the DCCT sensor.
(4)
Compressor failure
Refer to the following page(s).
[8-9-3 Checking the Compressor for Ground Fault and Coil Resistance Problems](page
266)
(5)
Inverter failure
Refer to the following page(s).
[8-9 Troubleshooting Inverter Problems (TLMU)](page 264)
Summary of Contents for R410A
Page 1: ......
Page 11: ... 2 HWE14080 GB ...
Page 25: ... 16 HWE14080 GB ...
Page 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Page 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Page 59: ... 50 HWE14080 GB ...
Page 71: ... 62 HWE14080 GB ...
Page 95: ... 86 HWE14080 GB ...
Page 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Page 123: ... 114 HWE14080 GB ...
Page 159: ... 150 HWE14080 GB ...
Page 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Page 309: ... 300 HWE14080 GB ...
Page 346: ......