[7-5 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
- 184 -
HWE14080
GB
7-5-21
Error Code [4240] (YLMU)
1. Error
code
definition
Overload protection
2. Error definition and error detection method
If the output current of "(Iac) >Imax (Arms)" or "THHS > TOL" is continuously detected for 10 minutes or more during inverter
operation.
Refer to the relevant pages for the details of model names and the specified values. [7-1-1 Inverter Protection Level Ta-
ble](page 155)
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems (YLMU)](page 276)
Cause
Check method and remedy
(1)
Air passage blockage
Check that the heat sink cooling air passage is not blocked
(2)
Power supply environment
Power supply voltage is 414 V or above.
(3)
Inverter failure
Refer to the following page(s). [8-10 Troubleshooting Inverter Problems (YL-
MU)](page 276)
(4)
Compressor failure
Check that the compressor has not overheated during operation.
ĺ
Check the refrigerant circuit (oil return section).
Refer to the following page(s). [8-10-3 Checking the Compressor for Ground
Fault and Coil Resistance Problems](page 278)
Summary of Contents for R410A
Page 1: ......
Page 11: ... 2 HWE14080 GB ...
Page 25: ... 16 HWE14080 GB ...
Page 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Page 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Page 59: ... 50 HWE14080 GB ...
Page 71: ... 62 HWE14080 GB ...
Page 95: ... 86 HWE14080 GB ...
Page 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Page 123: ... 114 HWE14080 GB ...
Page 159: ... 150 HWE14080 GB ...
Page 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Page 309: ... 300 HWE14080 GB ...
Page 346: ......