Error Code [4250] Detail Codes 103, 106, and 107 (TLMU)
1. Error
code
definition
DCCT overcurrent (H/W detection) (Detail code 103)
Instantaneous overcurrent (Detail code 106)
Overcurrent (effective value) (Detail code 107)
2. Error definition and error detection method
When a current above the specified value is detected by the electric current sensor.
Refer to the relevant pages for the details of model names and the specified values. [7-1-1 Inverter Protection Level Ta-
ble](page 155)
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-9 Troubleshooting Inverter Problems (TLMU)](page 264)
Cause
Check method and remedy
(1)
Inverter output
related
Refer to the following page(s).
[8-9-2 Checking the Inverter Board Error Detection Circuit](page 266)
[8-9-3 Checking the Compressor for Ground Fault and Coil Resistance Problems](page 266)
[8-9-4 Checking the Inverter for Damage at No-Load](page 267)
[8-9-5 Checking the Inverter for Damage during Compressor Operation](page 268)
[8-9-10 Checking the Installation Conditions](page 270)
Check the IGBT module resistance value of the INV board, if no problems are found.
[8-9-16 Troubleshooting Problems with IGBT Module](page 274)
Summary of Contents for R410A
Page 1: ......
Page 11: ... 2 HWE14080 GB ...
Page 25: ... 16 HWE14080 GB ...
Page 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Page 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Page 59: ... 50 HWE14080 GB ...
Page 71: ... 62 HWE14080 GB ...
Page 95: ... 86 HWE14080 GB ...
Page 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Page 123: ... 114 HWE14080 GB ...
Page 159: ... 150 HWE14080 GB ...
Page 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Page 309: ... 300 HWE14080 GB ...
Page 346: ......