[7-1 Error Code and Preliminary Error Code Lists ]
- 152 -
HWE14080
GB
4250
4255
4256
(Note)
4350
4355
4356
(Note)
[0]
Backup operation
O
[101]
IPM error
O
(page 185)
[103]
DCCT overcurrent (H/W detection)
O
(page 187)
[104]
Short-circuited IPM/Ground fault
O
(page 188)
[105]
Overcurrent error due to short-circuited motor
O
(page 189)
[106]
Instantaneous overcurrent (S/W detection)
O
(page 187)
(page 189)
[107]
Overcurrent (effective value)(S/W detection)
O
(page 187)
(page 189)
4260
-
-
Heatsink overheat protection at startup
O
(page 190)
5101
1202
-
Temperature sensor fault
Return air temperature
(TH21)
O
(page 191)
OA processing unit inlet
temperature (TH4)
O
(page 191)
5102
1217
-
Temperature sensor fault
Indoor unit pipe tempera-
ture (TH22)
O
(page 191)
OA processing unit pipe
temperature (TH2)
O
(page 191)
HIC bypass circuit outlet
temperature (TH2)
O
(page 192)
5103
1205
00
Temperature sensor fault
Indoor unit gas-side pipe
temperature (TH23)
O
(page 191)
OA processing unit gas-side
pipe temperature (TH3)
O
(page 191)
Pipe temperature at heatex-
changer outlet (TH3)
O
(page 192)
5104
1202
-
Temperature sensor fault
OA processing unit intake
air temperature (TH1)
O
(page 191)
Outside temperature
(TH24)
O
(page 191)
Detectable
only by the All-
Fresh type in-
door units
Outdoor unit discharge tem-
perature (TH4)
O
(page 192)
5105
1204
-
Temperature sensor fault
Accumulator inlet tempera-
ture (TH5)
O
(page 192)
5106
1216
-
Temperature sensor fault
HIC circuit outlet tempera-
ture (TH6)
O
(page 192)
5107
1221
-
Temperature sensor fault
Outside temperature (TH7)
O
(page 192)
5110
1214
[0]
Backup operation
O
01
Temperature sensor fault
Heatsink temperature
(THHS)
O
(page 193)
5201
-
-
High-pressure sensor fault (63HS1)
O
(page 194)
Error
Code
Prelimi-
nary
error
code
Error
(prelim-
inary)
detail
code
Error code definition
Searched unit
Notes
Outdoor unit
Indoor unit
LOSSNAY
Remote controller
Summary of Contents for R410A
Page 1: ......
Page 11: ... 2 HWE14080 GB ...
Page 25: ... 16 HWE14080 GB ...
Page 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Page 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Page 59: ... 50 HWE14080 GB ...
Page 71: ... 62 HWE14080 GB ...
Page 95: ... 86 HWE14080 GB ...
Page 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Page 123: ... 114 HWE14080 GB ...
Page 159: ... 150 HWE14080 GB ...
Page 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Page 309: ... 300 HWE14080 GB ...
Page 346: ......