[3-4 Functions of the Major Components of Indoor Unit ]
- 60 -
HWE14080
GB
3-4
Functions of the Major Components of Indoor Unit
Part
Name
Symbol
(functions)
Notes Usage
Specification Check
method
Linear
expan-
sion valve
LEV
1) Adjusts superheat at the
indoor heat exchanger
outlet during cooling
2) Adjusts subcool at the
heat exchanger outlet of
the indoor unit during
cooling
DC12V
Opening of stepping motor
driving valve 0-(1800) puls-
es
Refer to the section
"Continuity Test with a
Tester".
Continuity between
white, red, and or-
ange.
Continuity between
yellow, brown, and
blue.
Thermis-
tor
TH1
(Suction air
temperature)
Indoor unit control (Thermo)
0°C [32°F]:15kohm
10°C [50°F] :9.7kohm
20°C [68°F]:6.4kohm
25°C [77°F] :5.3kohm
30°C [86°F] :4.3kohm
40°C [104°F] :3.1kohm
Resistance check
TH2
(Pipe temper-
ature)
1) Indoor unit control (Frost
prevention, Hot adjust)
2) LEV control during heat-
ing operation (subcool
detection).
TH3
(Gas pipe
temperature)
LEV control during cooling op-
eration (superheat detection)
TH4
Outdoor air
temperature)
Indoor unit control (Thermo)
Temperature
sensor (In-
door air tem-
perature)
Indoor unit control (Thermo)
Yellow
White
Red
Orange
Brown Blue
M
1
273+t
R
0
=15k
R
0/80
=3460
Rt =
15exp{3460( - )}
1
273
Summary of Contents for R410A
Page 1: ......
Page 11: ... 2 HWE14080 GB ...
Page 25: ... 16 HWE14080 GB ...
Page 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Page 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Page 59: ... 50 HWE14080 GB ...
Page 71: ... 62 HWE14080 GB ...
Page 95: ... 86 HWE14080 GB ...
Page 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Page 123: ... 114 HWE14080 GB ...
Page 159: ... 150 HWE14080 GB ...
Page 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Page 309: ... 300 HWE14080 GB ...
Page 346: ......