[6-9 Evaluating and Adjusting Refrigerant Charge ]
- 129 -
HWE14080
GB
6
Test Run
1) Maximum refrigerant charge
There is a limit to the amount of refrigerant that can be charged into a unit. Regardless of the amount yielded by the formula
above, observe the maximum refrigerant charge in the table below.
*1 Maximum refrigerant charge: the amount of factory-charged refrigerant and the amount of refrigerant to be added on site.
Total index of the outdoor units
P72
P96
P120
P144
P168
P192
P216
Maximum refrigerant charge
*1
(kg)
32.7
41.7
49.5
50.0
58.7
66.0
74.6
Maximum refrigerant charge
*1
[lbs-oz]
72-1
91-15
109-2
110-4
129-7
145-8
164-7
Total index of the outdoor units
P240
P264
P288
P312
P336
P360
Maximum refrigerant charge
*1
(kg)
76.5
92.5
101.7
101.7
104.9
104.9
Maximum refrigerant charge
*1
[lbs-oz]
168-10
203-15
224-3
224-3
231-4
231-4