[7-7 Error Code Definitions and Solutions: Codes [6000 - 6999] ]
- 225 -
HWE14080
GB
7
Tro
ubles
hoot
in
g Us
in
g
Er
ror Codes
7-7-24
Error Code [6846]
1. Error
code
definition
Start-up time over
2. Error definition and error detection method
Start-up time over The unit cannot finish start-up process within 4 minutes after power on.
3. Cause, check method and remedy
Cause
Check method and remedy
(1)
Contact failure of indoor/outdoor unit connecting wire
Check disconnection or looseness or polarity
of indoor/outdoor unit connecting wire of in-
door and outdoor units.
(2)
Diameter or length of indoor/outdoor unit connecting wire is out
of specified capacity.
Check diameter and length of indoor/outdoor
unit connecting wire. Total wiring length: 80
m (including wiring connecting each indoor
unit and between indoor and outdoor unit)
Also check if the connection order of flat ca-
ble is S1, S2, S3.
(3)
2 or more outdoor units have refrigerant address "0". (In case of
group control)
Check if refrigerant addresses are overlap-
ping in case of group control system.
(4)
Noise has entered into power supply or indoor/outdoor unit con-
necting wire.
Check transmission path, and remove the
cause.
Note: The descriptions above, 1)-4), are for
EA, Eb and EC.
*The check code in the parenthesis indicates
PAR-30MAA model.
Summary of Contents for R410A
Page 1: ......
Page 11: ... 2 HWE14080 GB ...
Page 25: ... 16 HWE14080 GB ...
Page 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Page 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Page 59: ... 50 HWE14080 GB ...
Page 71: ... 62 HWE14080 GB ...
Page 95: ... 86 HWE14080 GB ...
Page 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Page 123: ... 114 HWE14080 GB ...
Page 159: ... 150 HWE14080 GB ...
Page 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Page 309: ... 300 HWE14080 GB ...
Page 346: ......