[2-4 M-NET Address Settings ]
- 21 -
HWE14080
GB
2
Re
st
ri
ct
io
n
s
2-4
M-NET Address Settings
2-4-1
Address Settings List
1. M-NET Address settings
(1) Address settings table
The need for address settings and the range of address setting depend on the configuration of the system.
*1. Address setting is not required for a City Multi system that consists of a single refrigerant circuit (with some exceptions).
*2. To set the ME remote controller address to "200", set the rotary switches to "00".
*3. To set the outdoor unit address to "100," set the rotary switches to "50."
*4. Some indoor units have 2 or 3 controller boards that require address settings.
No. 2 controller board address must be equal to the sum of the No. 1 controller board address and 1, and the No.3 controller board
address must equal to the No. 1 controller address and 2.
*5. The outdoor units in the same refrigerant circuit are automatically designated as OC, OS1, and OS2 in the order of capacity from large
to small (if two or more units have the same capacity, in the order of address from small to large).
Unit or controller
Symbol
Address
setting
range
Setting method
Factory
setting
CITY MULTI in-
door unit
Main/sub unit
IC
00,
01 to 50
*1
Assign the smallest address to the main indoor unit in
the group, and assign sequential address numbers to
the rest of the indoor units in the same group.
*4
00
M-NET adapter
M-NET control
interface
Free Plan
adapter
LOSSNAY, OA processing unit
Air handling kit
LC
00,
01 to 50
*1
Assign an arbitrary but unique address to each of these
units after assigning an address to all indoor units.
00
ME remote con-
troller
Main remote
controller
RC
101 to 150 Add 100 to the smallest address of all the indoor
units in the same group.
101
Sub remote
controller
RC
151 to
200
*2
Add 150 to the smallest address of all the indoor
units in the same group.
MA remote controller
MA
No address settings required. (The main/sub setting must be
made if 2 remote controllers are connected to the system.)
Main
CITY MULTI outdoor unit
OC,
OS1,
OS2
00,
51 to
100
*1,*3
Assign sequential addresses to the outdoor units
in the same refrigerant circuit. The outdoor units in
the same refrigerant circuit are automatically des-
ignated as OC and OS.
*5
00
System control-
ler
Group remote control-
ler
GR, SC
201 to 250 Assign an address that equals the sum of the
smallest group number of the group to be con-
trolled and 200.
201
System remote con-
troller
SR, SC
Assign an arbitrary but unique address within the
range listed on the left to each unit.
ON/OFF remote con-
troller
AN, SC
Assign an address that equals the sum of the
smallest group number of the group to be con-
trolled and 200.
Schedule timer (com-
patible with M-NET)
ST, SC
Assign an arbitrary but unique address within the
range listed on the left to each unit.
202
Centralized controller
AG-150A
GB-50ADA
GB-24A
TR, SC
000
201 to 250
Assign an arbitrary but unused address within the
range listed on the left to each unit. Be sure to set
it to "000" to control K-control units.
000
Expansion controller
PAC-YG50ECA
TR
000
201 to 250
Assign an arbitrary but unused address within the
range listed on the left to each unit. Be sure to set
it to "000" to control K-control units.
000
BM adapter
BAC-HD150
SC
000
201 to 250
Assign an arbitrary but unused address within the
range listed on the left to each unit. Be sure to set
it to "000" to control K-control units.
000
LM adapter
LMAP03U
SC
201 to 250 Assign an arbitrary but unique address within the
range listed on the left to each unit.
247
Summary of Contents for R410A
Page 1: ......
Page 11: ... 2 HWE14080 GB ...
Page 25: ... 16 HWE14080 GB ...
Page 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Page 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Page 59: ... 50 HWE14080 GB ...
Page 71: ... 62 HWE14080 GB ...
Page 95: ... 86 HWE14080 GB ...
Page 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Page 123: ... 114 HWE14080 GB ...
Page 159: ... 150 HWE14080 GB ...
Page 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Page 309: ... 300 HWE14080 GB ...
Page 346: ......