[7-6 Error Code Definitions and Solutions: Codes [5000 - 5999] ]
- 202 -
HWE14080
GB
7-6-14
Error Code [5301] Detail Code 120 (YLMU)
1. Error
code
definition
Faulty ACCT wiring (Detail code 120)
2. Error definition and error detection method
Presence of target current cannot be detected during the self-diagnostic operation immediately before startup.
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems (YLMU)](page 276)
7-6-15
Error Codes [5305, 5306] Detail Code 132
1. Error
code
definition
Position detection error at startup (Detail code 132)
2. Error definition and error detection method
When a motor sensor has detected an error within 10 seconds after the fan motor has gone into operation.
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s).
[8-9 Troubleshooting Inverter Problems (TLMU)](page 264)
[8-10 Troubleshooting Inverter Problems (YLMU)](page 276)
Cause
Check method and remedy
(1)
Inverter output wiring
problem
Check output wiring connections.
Confirm that the U- and W-phase output cables are put through CT12 and CT22 on
the INV board respectively.
(2)
Inverter failure
Refer to the following page(s).
[8-10-4 Checking the Inverter for Damage at No-Load](page 278)
[8-10-5 Checking the Inverter for Damage during Compressor Operation](page 279)
(3)
Compressor failure
Refer to the following page(s).
[8-10-3 Checking the Compressor for Ground Fault and Coil Resistance Prob-
lems](page 278)
Cause
Check method and remedy
(1)
Contact failure and faulty
fan motor wiring
Check the fan board connector CNINV and CNSNR for proper contacts.
Check the wirign betweem the fan motor and fan board.
(2)
Fan board failure
Refer to the following page(s).
(TLMU)
[8-9-9 Checking the Fan Inverter for Damage with Load](page 270)
(YLMU)
[8-10-9 Checking the Fan Inverter for Damage with Load](page 281)
(3)
Fan motor error
Refer to the following page(s).
(TLMU)
[8-9-6 Checking the Fan Motor for Ground Fault and Coil Resistance Prob-
lems](page 268)
(YLMU)
[8-10-6 Checking the Fan Motor for Ground Fault and Coil Resistance Prob-
lems](page 279)
Summary of Contents for R410A
Page 1: ......
Page 11: ... 2 HWE14080 GB ...
Page 25: ... 16 HWE14080 GB ...
Page 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Page 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Page 59: ... 50 HWE14080 GB ...
Page 71: ... 62 HWE14080 GB ...
Page 95: ... 86 HWE14080 GB ...
Page 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Page 123: ... 114 HWE14080 GB ...
Page 159: ... 150 HWE14080 GB ...
Page 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Page 309: ... 300 HWE14080 GB ...
Page 346: ......