[2-10 Restrictions on Refrigerant Pipes ]
- 46 -
HWE14080
GB
2-10-2
Restrictions on Refrigerant Pipe Size
(1) Diameter of the refrigerant pipe between the outdoor unit and the first branch (outdoor unit pipe size)
(2) Size of the refrigerant pipe between the first branch and the indoor unit (indoor unit pipe size)
(3) Size of the refrigerant pipe between the branches for connection to indoor units
Outdoor unit set name
(total capacity)
Liquid pipe size (mm) [inch]
Gas pipe size (mm) [inch]
72 model
ø9.52 [3/8"]
ø22.2 [7/8"]
96 model
ø9.52 [3/8"]
*1
*1. Use ø12.7 [1/2"] pipes if the furthest piping length (OU from IU) exceeds 90 m [295 ft].
ø22.2 [7/8"]
120 model
ø9.52 [3/8"]
*2
*2. Use ø12.7 [1/2"] pipes if the furthest piping length (OU from IU) exceeds 40 m [131 ft].
ø28.58 [1-1/8"]
144 model
ø12.7 [1/2"]
ø28.58 [1-1/8"]
168 model
ø15.88 [5/8"]
ø28.58 [1-1/8"]
192 model
ø15.88 [5/8"]
ø28.58 [1-1/8"]
216 model
ø15.88 [5/8"]
ø28.58 [1-1/8"]
240 model
ø15.88 [5/8"]
ø28.58 [1-1/8"]
264 - 312 model
ø19.05 [3/4"]
ø34.93 [1-3/8"]
336 - 360 model
ø19.05 [3/4"]
ø41.28 [1-5/8"]
model
Pipe diameter (mm) [inch]
06 - 15 models
Liquid pipe
ø6.35 [1/4"]
Gas pipe
ø12.7 [1/2"]
18 - 54 models
Liquid pipe
ø9.52 [3/8"]
Gas pipe
ø15.88 [5/8"]
72 model
Liquid pipe
ø9.52 [3/8"]
Gas pipe
ø19.05 [3/4"]
96 model
Liquid pipe
ø9.52 [3/8"]
Gas pipe
ø22.2 [7/8"]
Total capacity of the
downstream units
Liquid pipe size (mm) [inch]
Gas pipe size (mm) [inch]
- 54
ø9.52 [3/8"]
ø15.88 [5/8"]
P55 - P72
ø9.52 [3/8"]
ø19.05 [3/4"]
P72 - P108
ø9.52 [3/8"]
ø22.2 [7/8"]
P109 - P144
ø12.7 [1/2"]
ø28.58 [1-1/8"]
P145 - P240
ø15.88 [5/8"]
ø28.58 [1-1/8"]
P241 - P308
ø19.05 [3/4"]
ø34.93 [1-3/8"]
P309 -
ø19.05 [3/4"]
ø41.28 [1-5/8"]
Summary of Contents for R410A
Page 1: ......
Page 11: ... 2 HWE14080 GB ...
Page 25: ... 16 HWE14080 GB ...
Page 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Page 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Page 59: ... 50 HWE14080 GB ...
Page 71: ... 62 HWE14080 GB ...
Page 95: ... 86 HWE14080 GB ...
Page 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Page 123: ... 114 HWE14080 GB ...
Page 159: ... 150 HWE14080 GB ...
Page 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Page 309: ... 300 HWE14080 GB ...
Page 346: ......