[7-5 Error Code Definitions and Solutions: Codes [4000 - 4999] ]
- 188 -
HWE14080
GB
7-5-25
Error Codes [4250, 4255, 4256] Detail Code 104
1. Error
code
definition
Short-circuited IPM/Ground fault (Detail code 104)
2. Error definition and error detection method
When IPM/IGBT short damage or grounding on the load side is detected just before starting the inverter.
3. Cause, check method and remedy
In the case of 4250
In the case of 4255 and 4256
For inverter-related error codes, refer to the following page(s).
[8-9 Troubleshooting Inverter Problems (TLMU)](page 264)
[8-10 Troubleshooting Inverter Problems (YLMU)](page 276)
Cause
Check method and remedy
(1)
Grounding fault
compressor
Refer to the following page(s).
(TLMU)
[8-9-3 Checking the Compressor for Ground Fault and Coil Resistance Problems](page 266)
(YLMU)
[8-10-3 Checking the Compressor for Ground Fault and Coil Resistance Problems](page
278)
(2)
Inverter output
related
Refer to the following page(s).
(TLMU)
[8-9-2 Checking the Inverter Board Error Detection Circuit](page 266)
[8-9-3 Checking the Compressor for Ground Fault and Coil Resistance Problems](page 266)
[8-9-4 Checking the Inverter for Damage at No-Load](page 267)
[8-9-5 Checking the Inverter for Damage during Compressor Operation](page 268)
[8-9-10 Checking the Installation Conditions](page 270)
(YLMU)
[8-10-2 Checking the Inverter Board Error Detection Circuit](page 278)
[8-10-3 Checking the Compressor for Ground Fault and Coil Resistance Problems](page
278)
[8-10-4 Checking the Inverter for Damage at No-Load](page 278)
[8-10-5 Checking the Inverter for Damage during Compressor Operation](page 279)
[8-10-10 Checking the Installation Conditions](page 281)
Cause
Check method and remedy
(1)
Grounding fault
of fan motor
Refer to the following page(s).
(TLMU)
[8-9-6 Checking the Fan Motor for Ground Fault and Coil Resistance Problems](page 268)
(YLMU)
[8-10-6 Checking the Fan Motor for Ground Fault and Coil Resistance Problems](page 279)
(2)
Fan board fail-
ure
Refer to the following page(s).
(TLMU)
[8-9-7 Checking the Fan Board Error Detection Circuit at No Load](page 268)
[8-9-8 Checking the Fan Inverter for Damage at No Load](page 269)
[8-9-9 Checking the Fan Inverter for Damage with Load](page 270)
(YLMU)
[8-10-7 Checking the Fan Board Error Detection Circuit at No Load](page 279)
[8-10-8 Checking the Fan Inverter for Damage at No Load](page 280)
[8-10-9 Checking the Fan Inverter for Damage with Load](page 281)
Summary of Contents for R410A
Page 1: ......
Page 11: ... 2 HWE14080 GB ...
Page 25: ... 16 HWE14080 GB ...
Page 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Page 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Page 59: ... 50 HWE14080 GB ...
Page 71: ... 62 HWE14080 GB ...
Page 95: ... 86 HWE14080 GB ...
Page 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Page 123: ... 114 HWE14080 GB ...
Page 159: ... 150 HWE14080 GB ...
Page 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Page 309: ... 300 HWE14080 GB ...
Page 346: ......