[7-6 Error Code Definitions and Solutions: Codes [5000 - 5999] ]
- 196 -
HWE14080
GB
7-6-7
Error Code [5301] Detail Code 115 (YLMU)
1. Error
code
definition
ACCT sensor fault (Detail code 115)
2. Error definition and error detection method
When the formula "output current < 1.5 Arms" remains satisfied for 10 seconds while the inverter is in operation.
3. Cause, check method and remedy
For inverter-related error codes, refer to the following page(s). [8-10 Troubleshooting Inverter Problems (YLMU)](page 276)
Cause
Check method and remedy
(1)
Inverter open output phase
Check the output wiring connections.
(2)
Compressor failure
Refer to the following page(s).
[8-10-3 Checking the Compressor for Ground Fault and Coil Resistance Prob-
lems](page 278)
(3)
INV board failure
Refer to the following page(s).
[8-10-2 Checking the Inverter Board Error Detection Circuit](page 278)
[8-10-4 Checking the Inverter for Damage at No-Load](page 278)
[8-10-5 Checking the Inverter for Damage during Compressor Operation](page 279)
Summary of Contents for R410A
Page 1: ......
Page 11: ... 2 HWE14080 GB ...
Page 25: ... 16 HWE14080 GB ...
Page 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Page 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Page 59: ... 50 HWE14080 GB ...
Page 71: ... 62 HWE14080 GB ...
Page 95: ... 86 HWE14080 GB ...
Page 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Page 123: ... 114 HWE14080 GB ...
Page 159: ... 150 HWE14080 GB ...
Page 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Page 309: ... 300 HWE14080 GB ...
Page 346: ......