[5-2 Outdoor Unit Control ]
- 106 -
HWE14080
GB
5-2-14
Operation Mode
(1) Indoor unit operation mode
The operation mode can be selected from the following 5 modes using the remote controller.
(2) Outdoor unit operation mode
When the outdoor unit is performing a cooling operation, the operation mode of the connected indoor units that are not in the
cooling mode (Stopped, Fan, Thermo-OFF) cannot be changed to heating from the remote controller. If this attempt is mode,
"Heating" will flash on the remote controller. The opposite is true when the outdoor unit is performing a heating operation. (The
first selection has the priority.)
5-2-15
Demand Control
Cooling/heating operation can be prohibited (Thermo-OFF) by an external input to the indoor units.
When DIP SW6-8 is set to ON, the 4-step DEMAND control is enabled.
Eight-step demand control is possible in the system with two outdoor units.
Twelve-step demand control is possible in the system with three outdoor units.
For details, refer to the following page(s). [2-4-7 Various Control Methods Using the Signal Input/Output Connector on Outdoor
Unit](page 24)
5-2-16
Control of IH energization without the compressor in operation
IH is used to heat the compressor motor on the stopped outdoor unit to make liquid refrigerant in the compressor evaporate
or to keep liquid refrigerant from flooding the compressor.
Initial power on after power is turned on: Stays on for 12 hours, and then transitions to the operation that is performed while
the compressor is stopped
When the compressor is stopped: Stays on for 30 minutes after the compressor stopped, and then repeats the on-off cycle
at 30-minute intervals
1
Cooling mode
2
Heating mode
3
Dry mode
4
Fan mode
5
Stopping mode
1
Cooling mode
All indoor units in operation are in cooling mode.
2
Heating mode
All indoor units in operation are in heating mode.
3
Stopping mode
All indoor units are in fan mode or stopping mode.
Summary of Contents for R410A
Page 1: ......
Page 11: ... 2 HWE14080 GB ...
Page 25: ... 16 HWE14080 GB ...
Page 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Page 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Page 59: ... 50 HWE14080 GB ...
Page 71: ... 62 HWE14080 GB ...
Page 95: ... 86 HWE14080 GB ...
Page 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Page 123: ... 114 HWE14080 GB ...
Page 159: ... 150 HWE14080 GB ...
Page 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Page 309: ... 300 HWE14080 GB ...
Page 346: ......