[8-11 Control Circuit (TLMU) ]
- 288 -
HWE14080
GB
8-11-2
Troubleshooting Problems with Outdoor Unit Transmission Power Supply
Circuit
1) PUHY-P72, P96, P120, P144TLMU
Check the voltage between No.1 and No.2 pins of the
CN62 on the control board.
Check the wiring between the control board and power supply board
for the transmission line (CN62, CNPS, CN102 and CNIT),
and check for proper connection of connectors.
Check the wiring between the control board and power supply board
for the transmission line (CN62, CNPS, CN102 and CNIT), and check
for proper connection of connectors.
Is there a wiring
error or a connector
disconnection?
Check the voltage between No.5 and No.2 pins
of the CNPS on the control board.
Is the voltage
measurement between
4.5 and 5.2 VDC?
Is there a connector
disconnection?
Fix the connector disconnection.
Replace the M-NET board
Replace the M-NET board
Replace the inrush current
limiting resistor.
Replace the INV board.
Replace the INV board.
Check the wiring between the noise filter and the
INV board as well as screw tightness, and fix any
problems found.
Replace the noise filter.
Check and fix any power supply wiring and main power
supply problems found.
Check the inrush current resistance (R1).
Fix the wiring and connector
disconnection.
Check for shorted transmission
line for centralized control.
Replace the control board.
Check the voltage between No.1 and No.2 pins of the
CN62 on the power supply board for the transmission line.
Check the voltage between No.1 and No.3 pins of
the CNDC on the INV board.
Check the voltage between SC-P1 and TB-N on the INV board.
Check the voltages among SC-R, SC-S, and
SC-T on the INV board.
Check the voltages among TB21, TB22, and
TB23 on the noise filter.
Check the voltage at the power supply terminal block TB1.
DC24 ~ 30V
DC24 ~ 30V
DC24 ~ 30V
DC265 ~ 357V
DC265 ~ 357V
AC188 ~ 253V
AC188 ~ 253V
AC188 ~ 253V
DC24 ~ 30V
Turn on the
power again.
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
22 10%
Check the voltage at the indoor/outdoor
transmission terminal block (TB3) of outdoor unit.
DC 24 ~ 30 V
DC 24 ~ 30 V
Check the voltage at TB3 after removing transmission line from TB3.
Check whether the male connector is connected to
the female power supply connector (CN40).
Connected
Check voltage of terminal block for centralized control (TB7).
Check voltage of TB7 by removing transmission line from TB7.
Check if the indoor/outdoor transmission line is not
short-circuited, and repair the problem.
Check whether the transmission line is disconnected,
check for contact failure, and repair the problem.
Summary of Contents for R410A
Page 1: ......
Page 11: ... 2 HWE14080 GB ...
Page 25: ... 16 HWE14080 GB ...
Page 38: ... 2 6 System Connection Example 29 HWE14080 GB 2 Restrictions ...
Page 57: ... 2 10 Restrictions on Refrigerant Pipes 48 HWE14080 GB ...
Page 59: ... 50 HWE14080 GB ...
Page 71: ... 62 HWE14080 GB ...
Page 95: ... 86 HWE14080 GB ...
Page 121: ... 5 3 Operation Flowcharts 112 HWE14080 GB ...
Page 123: ... 114 HWE14080 GB ...
Page 159: ... 150 HWE14080 GB ...
Page 243: ... 7 8 Error Code Definitions and Solutions Codes 7000 7999 234 HWE14080 GB ...
Page 309: ... 300 HWE14080 GB ...
Page 346: ......