III
Outdoor Unit Components ]
- 60 -
HWE0803A
GB
[2] Control Box of the Outdoor Unit
1. PURY-P72THMU-A
1) Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the water-
proof and dust proof properties of the control box and may result in damage to its internal components.
2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter-
minals to remove them.
<HIGH VOLTAGE WARNING>
Control box houses high-voltage parts.
When opening or closing the front panel of the control box, do not let it come into contact with any of
the internal components.
Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes,
and Check that the voltage across terminals FT-P and FT-N (YHMU) on the INV board or the voltage at
both ends of the main capacitor (C1) (THMU) is 20VDC or below.
(It takes about 10 minutes to discharge electricity after the power supply is turned off.)
Electromagnetic relay(72C)
DC reactor (DCL)
Fan board
Rush current
protection resistor
(R1) Note.2
Noise filter
Note.2
Terminal block for
power supply
(TB1)
Note.1
Ground terminal
Smoothing capacitor(C1)
INV board
Terminal block for transmission line
(TB3, TB7)
M-NET board
Control board
Summary of Contents for PURY-P120Y(T)HMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 65: ... 56 ...
Page 89: ... 80 ...
Page 91: ... 82 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 115: ... 106 ...
Page 117: ... 108 ...
Page 133: ... 124 ...
Page 161: ... 152 ...
Page 163: ... 154 ...
Page 187: ... 178 ...
Page 341: ... 332 ...
Page 387: ......