VIII
Test Run Mode ]
- 173 -
HWE0803A
GB
Operation
Outdoor unit model
PURY-P168TSHMU-A
PURY-P96THMU-A
PURY-P72THMU-A
Model name of BC controller
CMB-P108NU-GA
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
21.1°C/- [70°F/-]
Outdoor
8.3°C/6.1°C [47°F/43°F]
Indoor unit
No. of connected units
Unit
5
No. of units in operation
5
Model
-
30/30/36/36/36
Piping
Main pipe
m
[ft]
5 [16-3/18"]
Branch pipe
10 [32-3/4"]
Total pipe length
55 [180-1/8"]
Fan speed
-
Hi
Amount of refrigerant
kg
[lbs-oz]
38.5 [85]
Outdoor
unit
Electric current
A
42.2
Voltage
V
230
Compressor frequency
Hz
71
48
LEV open-
ing
Indoor unit
Pulse
295/295/350/350
BC controller (1/2/3)
110/110/980
Pressure
High pressure(63HS1)/
Low pressure(63LS)
MPa
[psi]
2.64/0.68
[382/98]
2.64/0.69
[382/335]
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
2.60/2.27
[377/329]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C
[°F]
80 [176]
69 [156]
Heat exchanger outlet
(TH6)
0 [32]
0 [32]
Accumulator inlet
-2 [28]
1 [34]
Accumulator outlet
-3 [27]
1 [34]
Compressor inlet
-3 [27]
1 [34]
Compressor shell bottom
40 [104]
40 [104]
Indoor unit
LEV inlet
34 [93]
Heat exchanger inlet
67 [153]
Summary of Contents for PURY-P120Y(T)HMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 65: ... 56 ...
Page 89: ... 80 ...
Page 91: ... 82 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 115: ... 106 ...
Page 117: ... 108 ...
Page 133: ... 124 ...
Page 161: ... 152 ...
Page 163: ... 154 ...
Page 187: ... 178 ...
Page 341: ... 332 ...
Page 387: ......