IX
Troubleshooting ]
- 180 -
HWE0803A
GB
5102
1217
-
Temperature sensor
fault
Indoor unit pipe tempera-
ture (TH22)
O
OA processing unit pipe
temperature (TH2)
O
5103
1205
00
Temperature sensor
fault
Indoor unit gas-side pipe
temperature (TH23)
O
OA processing unit gas-
side pipe temperature
(TH3)
O
Pipe temperature at heat
exchanger outlet (TH3)
O
5104
1202
-
Temperature sensor
fault
OA processing unit intake
air temperature (TH1)
O
Outside temperature
(TH24)
O
Detectable
only by the All-
Fresh type in-
door units
Outdoor unit discharge
temperature (TH4)
O
5105
1204
-
Temperature sensor
fault
Accumulator inlet tempera-
ture (TH5)
O
5106
1216
-
Temperature sensor
fault
Heat exchanger inlet tem-
perature (TH6)
O
5107
1221
-
Temperature sensor
fault
Outside temperature (TH7)
O
5110
1214
01
Temperature sensor
fault
Heatsink temperature
(THHS)
O
5111
-
-
Temperature sensor
fault
(BC controller)
Liquid inlet temperature
(TH11)
O
5112
-
-
Bypass outlet temperature
(TH12)
O
5115
-
-
LEV3 outlet temperature
(TH15)
O
5116
-
-
LEV3 inlet temperature
(TH16)
O
5201
-
-
High-pressure sensor fault (63HS1)
O
5201
1402
-
High-pressure sensor fault
(Outdoor unit HPS/BC controller PS1)
O
O
5203
-
-
Intermediate pressure sensor fault
(BC controller PS3)
O
5301
4300
[115]
ACCT sensor fault
O
[117]
ACCT sensor circuit fault
O
[119]
Open-circuited IPM/Loose ACCT connector
O
[120]
Faulty ACCT wiring
O
5401
-
-
Temperature sensor fault
O
5701
-
-
Loose float switch connector
O
Error
Code
Prelimi-
nary
error
code
Error
(prelim-
inary)
detail
code
Error code definition
Searched unit
Notes
Outdoor unit
Indoor unit
BC controller
LOSSNAY
Remote controller
Summary of Contents for PURY-P120Y(T)HMU-A
Page 1: ......
Page 11: ... 2 ...
Page 25: ... 16 ...
Page 65: ... 56 ...
Page 89: ... 80 ...
Page 91: ... 82 ...
Page 99: ... 90 ...
Page 101: ... 92 ...
Page 115: ... 106 ...
Page 117: ... 108 ...
Page 133: ... 124 ...
Page 161: ... 152 ...
Page 163: ... 154 ...
Page 187: ... 178 ...
Page 341: ... 332 ...
Page 387: ......