IX
Troubleshooting ]
- 208 -
HWE0803A
GB
1. Error
Code
Overload protection
2. Error definition and error detection method
If the output current of "(Iac) >Imax (Arms)" or "THHS > TOL" is continuously detected for 10 minutes or more during inverter
operation.
3. Cause, check method and remedy
Refer to section -7- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the
inverter.(page 293)
4240
(THMU-A)
Model
Imax(Arms)
P72 model
35
P96, P120 model
53
Model
TOL
P72 model
95°C [203°F]
P96, P120 model
80°C [175°F]
Cause
Check method and remedy
(1)
Air passage blockage
Check that the heat sink cooling air passage is not blocked
(2)
Power supply environment
Power supply voltage is 188 V or above.
(3)
Inverter failure
Refer to IX [4] -7-.(page 293)
(4)
Current sensor (ACCT) failure
Refer to IX [4] -7- (4).
(5)
Compressor failure
Check that the compressor has not overheated during operation.
-> Check the refrigerant circuit (oil return section).
Refer to IX [4] -7- (2) [2].(page 295)